Table A-3 DC Power Entry Module Electrical Specifications

Description

Value

 

 

Rated input voltage1

–48 VDC nominal in North America

 

–60 VDC nominal in the European Community

 

(range: –40.5 to –75 VDC)

 

 

Input current rating1

60A maximum @ 40.5 VDC

Source DC service

60A

requirement1

 

Nominal output voltage

–48 VDC @ 40A maximum

and current

 

 

 

Total DC input power

1630 VA (original series)

 

2600 VA (enhanced series)

 

 

Redundancy

2 DC-input PEMs are required for 2N redundancy

 

 

1. For each DC-input PEM.

 