Integra RDC-7.1 instruction manual Effective Sensor Layout, Effective Sensor Connections

Models: RDC-7.1

1 156
Download 156 pages 25.69 Kb
Page 46
Image 46
Effective Sensor Layout

Connecting Components not Reached by the Remote Controller Signals (IR IN) – USA and Canadian models –

In order to use the remote controller to control the RDC-7.1 from a remote location, you will need to pre- pare a multiroom kit (sold separately) such as one listed below:

Multiroom kits such as those made by Niles® and Xantech®

RF Receivers can also be used with the remote controller to control the RDC-7.1 from a remote location. To use RF Receivers, set the Transmission Signal Format set- ting to “RF” (See page 141 for details).

If Remote Controller Signal Does not Reach the RDC-7.1 Remote Sensor

Effective Sensor Layout

Example for the main room

If the RDC-7.1 is located inside a cabinet or other enclosure where the infrared rays from the remote controller cannot enter, then operation with the remote controller will not be possible. In such a case, it will be necessary to install a remote sensor at a location outside of the cabinet so that the infrared rays from the controller can be sensed.

 

Connecting

IR Receiver

 

 

IR IN

block

 

 

 

RDC-7.1

 

 

 

Remote controller

In the

 

Main room

cabinet

 

 

 

 

 

: Signal flow

Example for the remote zone (Zone 2/Zone 3)

The IR IN input allows you to control the RDC-7.1 from the remote zone (Zone 2/Zone 3) with the remote controller even though the remote zone may be on the other side of the building from the main zone. The diagram below shows how to make the proper connections for the remote zone.

To IR IN

 

IR Receiver

RDC-7.1

 

Connecting

block

 

 

Remote controller

Main room

Zone 2/Zone 3 room

 

: Signal flow

Effective Sensor Connections

When connecting a multiroom kit, use the IR connection Phoenix (Pluggable connector) terminal (smaller one) supplied with the RDC-7.1.

Connect the ribbon cable from the connecting block to the IR connection Phoenix terminal.

1.Loosen the screws using a flatblade screwdriver to open the shutters.

2.Connect the white wire to the MAIN, ZONE 2 or ZONE 3 terminal according to the room where the multiroom kit is used, and then close the shutter.

3.Connect the red wire to the +12V terminal, and then close the shutter. If you use more than one multi room kit in different rooms such as MAIN and ZONE 2, connect all the red wires to the +12V ter- minal together.

4.Connect the black wire to the GND terminal, and then close the shutter. If you use more than one multi-room kit in different rooms, connect all the black wires to the GND terminal together.

Ribbon cable

Red

Black

White

Flatblade

+12Vscrewdriver

GND

IN

When the multiroom kits are used for all the rooms

From Main room

Red

 

 

 

ZONE 2

White

+12V

GND

Red

 

 

MAIN

ZONE 3

White

ZONE 2

Red

ZONE 3

 

 

 

 

White

 

5.As shown in the illustration below, connect the Phoe- nix terminal firmly to the IR IN socket on the RDC-7.1.

Push the connec- tor into the socket until it clicks.

46

Page 46
Image 46
Integra RDC-7.1 instruction manual Effective Sensor Layout, Effective Sensor Connections