Application planning 4.4 Mounting Positions and Fastening
Note
The computer unit with AC power supply satisfies fire protection requirements to
•Provide adequate volume in the switchgear cabinet for air circulation and heat transport. Keep at least 10 cm distance between the device and switchgear cabinet.
•Ensure that the maximum air intake temperature, measured 10 cm before the air intake opening on the fan, does not exceed 45°C. The maximum air intake temperature must be accounted for especially when sizing closed switchgear cabinets.
•The minimum distance between the device and the housing is 10 cm on the air output side at the fan.
•Position the device in such a way that the air vents of the housing are not covered up following mounting.
•Ensure there is enough free space in the switchgear cabinet to allow the sheet metal cover to be removed. You will otherwise have to remove the device from the switchgear cabinet or swivel arm when replacing memory or the battery.
•Provide enough free space to add on to the device.
•Equip the switchgear cabinet with struts for stabilizing the mounting
•Avoid extreme environmental operating conditions. Protect your device against dust, moisture and heat.
•Install the device in such a way (see ChapterTechnical specifications) that it poses no danger, e.g. by falling over.
•During assembly, please comply with the approved installation positions.
Notice
If you mount the device in an impermissible installation position or you do not observe the environmental conditions (see ChapterTechnical specifications), you endanger the product safety provided by the
For additional information, refer to the dimension diagrams in the appendix.
SIMATIC Panel PC 877 | |
Operating instructions, Release 07/2006, |