Alphabetical reference

 

Commands and Queries Reference

DSP

remove a user message from the XMP 2600 front panel display.

 

Syntax

DSP

 

 

Parameters

none

 

 

Category

System

Type: Sequential

DSP

display a message on the XMP 2600 front panel display.

 

Syntax

DSP <string>

 

 

Parameters

the message to be displayed, limited to 21

 

 

characters. Extra characters are truncated.

 

Category

System

Type: Sequential

ERR?

return the last known Error Code of the XMP 2600 main controller.

 

The error code is cleared.

 

 

Syntax

ERR?

 

 

Parameters

none

 

 

Category

Status

Type: Sequential

ERR?

return the last know Power Module error code. The error code is

 

cleared.

 

 

 

Syntax

ERR? <ch>

 

 

Parameters

the number of the channel to be queried.

 

Category

Status

Type: Sequential

FOLD

program the type of Foldback to be used by the Power Module when

 

Current Limit is reached.

 

 

Syntax

FOLD <ch>,<int>

 

 

Parameters

the number of the Power Module to be programmed.

 

 

the type of Foldback - a decimal value in the range 0

 

 

to 4, as detailed below:

 

 

 

0 = no Foldback

 

 

 

1 = retry Foldback

 

 

 

2 = linear Foldback

 

 

 

3 = nonlinear Foldback

 

 

 

4 = shutdown Foldback

 

 

 

See the “current limiting schemes” section of the

 

 

Basic Programming chapter for details on Foldback

 

 

behavior.

 

 

Category

Settings

Type: Overlapped

FOLD?

return the current Foldback selection of the Power Module.

 

Syntax

FOLD? <ch>

 

 

Parameters

the number of the channel to be queried.

 

Category

Settings

Type: Sequential

48

XMP 2600 Programming Manual rev. 1.1

Page 61
Image 61
Xantrex Technology manual Remove a user message from the XMP 2600 front panel display