Commands and Queries Reference

 

Alphabetical reference

GLBL

inform the XMP 2600 Main Controller on shut-down behavior of the

 

installed Power Modules.

 

 

Syntax

GLBL <int>,<int>

 

 

Parameters

the two integers are (respectively) the high and low

 

 

parts of a 16 bits word where each bit represent a

 

 

Power Module. If the bit value is “0” then that

 

 

Power Module will not globally shut-down when

 

 

faulty. If the bit value is ”1” then this Power Module

 

 

will cause a global shut-down when it is faulty.

 

 

Works in combination with the GRP command.

 

Category

System

Type: Sequential

GLBL?

return the current Global Shut-down set-up of all Power Modules. The

 

response is made up of two decimal numbers (each in the range 0 to

255)being the high (sent first) and low parts of a 16 bits word. Each bit in the response represents the Global set-up of a Power Module (see GLBL command for details on bit values).

 

Syntax

GLBL?

 

 

Parameters

none

 

 

Category

System

Type: Sequential

GPIB

set-up the operating mode of the XMP 2600. Re-calculate <rqs>.

 

Syntax

GPIB <int>

 

 

Parameters

the mode the XMP 2600 is to be operating in: a

 

 

value of “1” is for the IEEE 488.2 compatible mode.

 

Category

System

Type: Sequential

GPIB?

return the

current operating mode of the XMP 2600. The value

 

returned is a decimal number in the range 0 to 1.

 

 

Syntax

GPIB?

 

 

Parameters

none

 

 

Category

System

Type: Sequential

GRP

define the members of the group of Power Modules to be shutdown

 

when one (or more) is faulty.

 

 

Syntax

GRP <int>,<int>

 

 

Parameters

the two integers are (respectively) the high and low

 

 

parts of a 16-bit word where each bit represents a

 

 

Power Module. If the bit value is “0” then that

 

 

Power Module is not part of the group. If the bit

 

 

value is ”1” then this Power Module will be

 

 

shutdown when any of the group’s members is

 

 

faulty.

 

 

Category

System

Type: Sequential

XMP 2600 Programming Manual rev. 1.1

49

Page 62
Image 62
Xantrex Technology manual Set-up the operating mode of the XMP 2600. Re-calculate rqs