Input Mains

Input Mains

Voltage

Rating

The XMP 2600 operates at the following mains nominal voltages:

170Vac - 265Vac nominal (45 to 66Hz)

120Vac nominal, up to 1KW output power (45 to 66Hz)

Do not exceed this voltage range (nominal), as deterioration of performance or damage to the unit is likely to occur. The following table shows the mains voltage specification of the Power Supply:

Do Not Open The Unit

Air Inlets And Air Outlet

Output

Voltages

Nonoperative Modules

Nominal Mains

Nominal Current

230Vac

Iin<15A

 

 

120Vac, Po<1KW

Iin<15A

 

 

Mains supply voltage fluctuations may not exceed +/-10% of the nominal voltage.

Power plug shall be fitted according to each national electrical code, and rated for a current of at least 20A.

WARNING

The XMP 2600 must be operated at the proper mains voltage. Before operating the unit make sure the mains voltage complies with the range described above. Noncompliance with the input voltage may cause hazard and damage to the unit!

The user, except when replacing modules, should not open the unit.

WARNING

Make sure the power cord is disconnected from the mains before opening the unit. High voltages inside the unit may cause electric shock.

The Power Supply is a forced air-cooled unit. Cooling is essential for the unit's proper operation.

The unit includes four air inlet openings located in the front panel, in both the left and right sides near the front panel and in the top cover near the front panel. The air outlet is in the rear panel (all over its surface).

Make sure there are no obstructions for the airflow, at least two centimeters (0.8”) away from these openings.

Obstructing these ventilation openings may cause fire and irreversible damage to the unit.

The Power Supply's outputs (at the unit's rear) may carry high voltages. Make sure to handle them properly to avoid shock hazard.

Unused outputs must be closed with load connectors (these connectors must include sense lines connections).

Do not operate the unit if it contains damaged or defective modules. Hazard or damage may occur.

Damaged or defective units should be repaired by authorized personnel only.