ADC Telecommunications, Inc.
154 CHAPTER 8: TIMING AND ALARM CONTROLLER MANAGEMENT
To configure the faults for which you want to be notified, perform the following tasks. By default, the fault reporting status is “disabled” for each fault:
ps-ac The power supply associated with the chassis
detected the loss of one or more AC inputs.
ps-dc The power supply associated with the chassis
detected a DC out-of-range fault.
ps-temp The power supply associated with the chassis
detected an over-temperature condition.
red-alarm One or more payload blades has asserted a
Red Alarm.
yellow alarm One or more payload blades has asserted a
Yellow Alarm.
Task Command
1. Enter root mode. root
2. Specify the faults that you
want reported.
chassis-fault {backplane |
backplane-power |
backplane-power-a |
backplane-power-b |
backplane-temp |
bits-a |
bits-b |
blue |
fan-rotation |
fan-temp |
local-pwr-a |
local-pwr-b |
processor-temp |
ps-ac |
ps-dc |
ps-temp |
red-alarm |
yellow}
Fault Description