Cisco Systems 11500 Series manual Connecting the Chassis to Ground, Tools and Supplies, 2-22

Models: 11500 Series

1 206
Download 206 pages 7.48 Kb
Page 78
Image 78
Connecting the Chassis to Ground

Chapter 2 Cabling the CSS

Connecting the Chassis to Ground

Connecting the Chassis to Ground

Connecting the CSS 11503 or CSS 11506 chassis to earth ground is required for all DC-powered installations, and any AC-powered installation where compliance with Telcordia (formerly Bellcore) grounding requirements is necessary. Have the recommended tools and supplies available before you begin this procedure (see Table 2-8).

Warning Never defeat the ground conductor or operate the equipment in the absence of a suitably installed ground conductor. Contact the appropriate electrical inspection authority or an electrician if you are uncertain that suitable grounding is available.

Tools and Supplies

The accessory kit shipped with the CSS contains the following items used in this procedure:

One 2-hole grounding lug (Panduit no. LCD6-10A-L)

Two M5 screws for the grounding lug

Table 2-8lists the other tools, equipment, and supplies that you need to connect system ground to the chassis. These are items that you must supply.

Table 2-8 Tools and Supplies

 

 

 

Quantity

Description

 

Comments

 

 

 

 

 

1

Number 2 Phillips screwdriver

 

 

 

 

 

 

1

Wire stripping tool

 

Choose a tool that does not nick

 

 

 

 

 

 

the wire.

 

 

 

 

 

 

 

 

 

 

Varies

Grounding wire

 

6 AWG, 0.204 in. (5.18 mm)

 

 

 

 

 

 

recommended. The wire should

 

 

 

 

 

 

have applicable agency

 

 

 

 

 

 

approvals such as Telcordia.

 

 

 

 

 

 

 

 

 

 

Varies

Screws to attach ground wire to

 

Part requirements depend on

 

 

 

 

grounding point at site

 

location.

 

 

 

 

 

 

 

 

 

 

Cisco 11500 Series Content Services Switch Hardware Installation Guide

 

 

 

 

 

 

2-22

 

 

 

 

 

78-13884-03

 

 

 

 

 

 

 

Page 78
Image 78
Cisco Systems 11500 Series manual Connecting the Chassis to Ground, Tools and Supplies, 2-22