Environmental specifications
40 °C to 45 °C (104 °F to 113 °F) | Maximum temperature is reduced by 1°C/125 m |
| (1°F/228 ft) above 950 m (3,117 ft). |
Particulate contamination |
|
NOTE: This section defines the limits to help avoid IT equipment damage and/or failure from particulates and gaseous contamination. If it is determined that levels of particulates or gaseous pollution are beyond the limits specified below and are the reason for the damage and/or failures to your equipment, it may be necessary for you to
Air filtration
NOTE: Applies to data center environments only. Air filtration requirements do not apply to IT equipment designed to be used outside a data center, in environments such as an office or factory floor.
Conductive dust
NOTE: Applies to data center and
Corrosive dust
NOTE: Applies to data center and
Gaseous contamination
Data center air filtration as defined by ISO Class 8 per ISO
NOTE: Air entering the data center must have MERV11 or MERV13 filtration.
Air must be free of conductive dust, zinc whiskers, or other conductive particles.
•Air must be free of corrosive dust.
•Residual dust present in the air must have a deliquescent point less than 60% relative humidity.
NOTE: Maximum corrosive contaminant levels measured at ≤50% relative humidity.
Copper coupon corrosion rate | <300 Å/month per Class G1 as defined by ANSI/ |
| |
Silver coupon corrosion rate | <200 Å/month as defined by AHSRAE TC9.9. |
Expanded operating temperature
NOTE: When operating in the expanded temperature range, system performance may be impacted.
NOTE: When operating in the expanded temperature range, ambient temperature warnings may be reported on the LCD and in the System Event Log.
Continuous operation | 5°C to 40°C at 5% to 85% RH with 29°C dew point. |
NOTE: Outside the standard operating temperature (10°C to 35°C), the system can operate continuously down to 5°C or as high as 40°C.