Expanded operating temperature

 

For temperatures between 35°C and 40°C, de-

 

rate maximum allowable temperature by 1°C per

 

175 m above 950 m (1°F per 319 ft).

< 1% of annual operating hours

–5°C to 45°C at 5% to 90% RH with 29°C dew

 

point.

 

NOTE: Outside the standard operating

 

temperature (10°C to 35°C), the system can

 

operate down to –5°C or up to 45°C for a

 

maximum of 1% of its annual operating hours.

 

For temperatures between 40°C and 45°C, de-

 

rate maximum allowable temperature by 1°C per

 

125 m above 950 m (1°F per 228 ft).

Expanded Operating Temperature Restrictions

• You must have six fans configured on your

 

system.

 

• Do not perform a cold startup below 5°C.

 

• The operating temperature specified is for a

 

maximum altitude of 3048 m (10,000 ft).

 

• Express Flash is not supported.

 

• GPU is not supported.

 

• 160 W workstation CPU is not supported.

 

• Internal TBU (Tape Backup Unit) is not

 

supported.

 

• Two power supplies in redundant mode are

 

required, but do not support PSU failure

 

function.

 

• Non Dell qualified peripheral cards and/or

 

peripheral cards greater than 25 W are not

 

supported.

 

• PCIeSSD is not supported.

 

• Eighteen 3.5 inch hard-drive configuration is

 

not supported.

 

• Fusion IO is not supported.