Expanded operating temperature
| For temperatures between 35°C and 40°C, de- |
| rate maximum allowable temperature by 1°C per |
| 175 m above 950 m (1°F per 319 ft). |
< 1% of annual operating hours | |
| point. |
| NOTE: Outside the standard operating |
| temperature (10°C to 35°C), the system can |
| operate down to |
| maximum of 1% of its annual operating hours. |
| For temperatures between 40°C and 45°C, de- |
| rate maximum allowable temperature by 1°C per |
| 125 m above 950 m (1°F per 228 ft). |
Expanded Operating Temperature Restrictions | • You must have six fans configured on your |
| system. |
| • Do not perform a cold startup below 5°C. |
| • The operating temperature specified is for a |
| maximum altitude of 3048 m (10,000 ft). |
| • Express Flash is not supported. |
| • GPU is not supported. |
| • 160 W workstation CPU is not supported. |
| • Internal TBU (Tape Backup Unit) is not |
| supported. |
| • Two power supplies in redundant mode are |
| required, but do not support PSU failure |
| function. |
| • Non Dell qualified peripheral cards and/or |
| peripheral cards greater than 25 W are not |
| supported. |
| • PCIeSSD is not supported. |
| • Eighteen 3.5 inch |
| not supported. |
| • Fusion IO is not supported. |
179