Hardware Information

Rack Mounting Installation

Rack shown in illustration is not included with Digi CM.

1.Attach enclosed bracket ears to rack as shown in illustration.

2.Follow safety precautions when placing Digi CM on rack.

Rack Mounting Safety Precautions

Distribute weight evenly in the rack to avoid overloading.

Ensure proper ventilation with at least 12 inches (30 centimeters) of clearance on all sides.

Check equipment nameplate ratings before connecting to the supply circuit to avoid overloads which may damage over-current protection devices and supply wiring.

Maintain reliable earthing for rack-mounting equipment, especially for supply connections.

Install equipment in Restricted Access Areas only (dedicated equipment rooms/closets) in accordance with Articles 110-16, 110-17, and 110-18 of the National Electrical Code, ANSI/NFPA 70.

Connect equipment to a DC supply source (reliably earthed) that is electrically isolated from the AC source.

Directly connect the equipment chassis to the DC supply system-grounding electrode conductor or a bonding jumper from a grounding terminal bar (or bus) that is connected to the DC supply system grounding electrode conductor.

Contain equipment that has a connection between the grounded conductor of the same DC supply circuit, the grounding conductor, and also the point of grounding of the DC system in the same immediate area. Do not ground the equipment elsewhere.

Chapter 17

149

Page 149
Image 149
Digi Digi CM manual Rack Mounting Installation