Emerson 400518-01 Cable to Enclosure Shielding, Through Wall Shield Grommet, Installation

Models: 400518-01

1 88
Download 88 pages 22.24 Kb
Page 18
Image 18
Cable to Enclosure Shielding

Safety Information

Product Overview

 

 

Installation

Diagnostics

Options and Accessories

Specification

Cable to Enclosure Shielding

Shielded motor, feedback, serial communications and external encoder cables were used for compliance testing and are necessary to meet the EMC requirements. Each cable shield was grounded at the enclosure wall by the type of grommet described earlier and shown in the following figure.

Outside Enclosure

O-Ring seals against outside of enclosure to meet IP68 (comparable to NEMA 6)

Spring Contacts

Cable Shielding

Cable Jacket

Inside Enclosure

When Lock Nut is tightened to inside of enclosure, lock nut will cut through varnished, anodized, and powder coated finishes. Tighten lock nut so it cuts through the finish and into housing.

Remove 1/2 to 1 inch of cable jacket.

The Spring Contacts will make a continuous electrical path from the shield of the cable to equipment ground.

After tightening lock nut and positioning cable so that Spring Contacts are contacting the cable shield, tighten Cable Seal Housing.

Figure 3:

Through Wall Shield Grommet

 

 

 

 

 

 

Cable Type

 

Cable Model

Shielded Cable Grommet

Actual Hole Size

 

Kit Model

 

 

 

 

Motor Cable, 18 Ga

XTMDS

CGS-047

0.8125 or 13/16"

 

 

 

 

 

Motor Cable, 16 Ga

CMDS

CGS-047

0.8125 or 13/16"

 

 

 

4X16SS

CGS-047

0.8125 or 13/16"

 

 

 

 

 

 

Motor Cable, 18 Ga

XCMDS

CGS-047

0.8125 or 13/16"

 

 

 

 

 

Motor Cable, 12 Ga

CMMS

CGS-069

1.125 or 1 1/8"

 

 

 

4X12SS

CGS-069

1.125 or 1 1/8"

 

 

 

 

 

 

 

Feedback Cable

CFOS

CGS-047

0.8125 or 13/16"

 

 

 

MGFS

CGS-047

0.8125 or 13/16"

 

 

 

 

 

 

 

Flex Motor Cable, 16 Ga

CMDF

CGS-047

0.8125 or 13/16"

 

 

 

4X16SF

CGS-047

0.8125 or 13/16"

 

 

 

 

 

 

 

Flex Motor Cable, 12 Ga

CMMF

CGS-069

1.125 or 1 1/8"

 

 

 

4X12SF

CGS-069

1.125 or 1 1/8"

 

 

 

 

 

 

 

 

 

CFCF

CGS-069

1.125 or 1 1/8"

 

 

 

 

Flex Feedback Cable

CFOF

CGS-069

1.125 or 1 1/8"

 

 

 

 

 

 

 

MGFF

CGS-069

1.125 or 1 1/8"

 

 

 

 

External Encoder

ENCO

CGS-047

0.8125 or 13/16"

 

 

 

 

 

AC Power

 

user supplied

user supplied

user supplied

 

 

 

 

 

6

Page 18
Image 18
Emerson 400518-01 installation manual Cable to Enclosure Shielding, Through Wall Shield Grommet, Installation