Emerson 400518-01 installation manual Line Fusing and Wire Size, Ferraz, Square D, Line Wire Gauge

Models: 400518-01

1 88
Download 88 pages 22.24 Kb
Page 28
Image 28
Line Fusing and Wire Size

Safety Information

Product Overview

 

 

Installation

Diagnostics

Options and Accessories

Specification

Line Fusing and Wire Size

You must incorporate over current protection for the incoming AC power with the rating shown here.

UL approval for operation with the circuit breakers identified in the table below is pending. At present, fuses shown must be used for installation to meet UL.

 

Recommended

 

Fuse

 

Miniature Circuit Breaker

Drive Model

Minimum AC/PE

Fuse Class & Action

Bussman

Ferraz-

Allen Bradley

Square D

 

Line Wire Gauge

 

Shawmut

 

 

 

 

 

 

 

 

RK1 Time-Delay

LPN-RK-6SP

A2D6R

1489-A1D060

60124

EP202

16 AWG

RK1 Quick-Acting

KTN-R-6

A2K6R

6 A, 1 pole

6 A. 1 pole

 

 

 

 

 

 

 

ISO 1,5

 

 

 

 

 

CC Time-Delay

LP-CC-6

ATDR6

1489-A2 D060

60158

 

 

 

 

 

 

 

 

6 A, 2 pole

6 A, 2 pole

 

 

CC Quick-Acting

KTK-R-6

ATMR6

 

 

 

 

 

 

 

 

 

 

 

 

 

RK1 Time-Delay

LPN-RK-10SP

A2D10R

1489-A1D100

60127

EP204

16 AWG

RK1 Quick-Acting

KTN-R-10

A2K10R

10 A, 1 pole

10 A, 1 pole

 

 

 

 

 

 

 

ISO 1,5

 

 

 

 

 

CC Time-Delay

LP-CC-10

ATDR10

1489-A2D100

60161

 

 

 

 

 

 

 

 

10 A, 2 pole

10 A, 2 pole

 

 

CC Quick-Acting

KTK-R-10

ATMR10

 

 

 

 

 

 

 

 

 

 

 

 

 

RK1 Time-Delay

LPN-RK-15SP

A2D15R

1489-A1D150

60129

EP206

14 AWG

RK1 Quick-Acting

KTN-R-15

A2K15R

15 A, 1 pole

15 A, 1 pole

 

 

 

 

 

 

 

ISO 2,5

 

 

 

 

 

CC Time-Delay

LP-CC-15

ATDR15

1489-A2D150

60263

 

 

 

 

 

 

 

 

15 A, 2 pole

15 A, 2 pole

 

 

CC Quick-Acting

KTK-R-15

ATMR15

 

 

 

 

 

 

 

 

 

 

 

Use copper conductors only. Conductors must be rated 75°C or higher, preferably 90°C.

The Protective Earth (PE) wire connection is mandatory for human safety and proper operation. This connection must not be fused or interrupted by any means. Failure to follow proper PE wiring can cause death or serious injury.

.

Drive Model

Input Voltage

Frequency

Input Current (Amps RMS) at

Inrush Current

(Vac)

(Hz)

Full Drive Output Current

(Amps)

 

EP202

 

 

5.0

40 (5 ms)

 

 

 

 

 

EP204

240 / 1 Ø

47 - 63

8.5

65 (5 ms)

 

 

 

 

 

EP206

 

 

12.0

100 (5 ms)

 

 

 

 

 

This inrush current specification assumes the drive has been powered off for at least 8 minutes at 40ºC (104ºF) ambient or 5 minutes at 25ºC (77ºF) ambient. If this amount of time has not elapsed since power off, the inrush current will be higher.

16

Page 28
Image 28
Emerson 400518-01 Line Fusing and Wire Size, Ferraz, Square D, Line Wire Gauge, Full Drive Output Current