Drive Overload Protection

Solid state motor overload protection is provided in each model at no more than 115% of rated FLA. This overload protection is based on maximum continuous output current capacity. It will allow up to 200 percent of drive FLA to be delivered for the amount of time determined by the following chart.

Drive Output Current vs. Time graph

 

60

 

 

 

 

 

50

 

 

 

 

(seconds)

40

 

 

 

 

30

 

 

 

 

 

 

 

 

 

Time

20

 

 

 

 

 

 

 

 

 

 

10

 

 

 

 

 

0

 

 

 

 

 

100

125

150

175

200

% Drive Rated Current

When motor rated FLA is less than drive FLA, the motor FLA parameter is to be entered into drive configuration. Drive will then provide motor overload protection at correct value.