Panel Layout

Safety Information

Product Overview

 

 

Installation

Diagnostics

Options and Accessories

Specification

You should consider future troubleshooting and repair when installing all wiring. All wiring should be either color coded and/or tagged with industrial wire tabs.

As a general rule, the minimum cable bend radius is ten times the cable outer diameter.

All wiring and cables, stationary and moving, must be protected from abrasion.

Ground wires should not be shared or "daisy-chained" with other equipment.

Ensure that full metal to metal surface contact is made between the enclosure ground lug and the metal enclosure, not simply through the mounting bolt and threads.

All inductive coils must be suppressed with appropriate devices, such as diodes or resistor/capacitor (RC) networks, except as described in this manual.

If using a non-shielded Ethernet cable, install a clamp on ferrite, Control Techniques part number 157016-07, Steward 28A0593-0A2 or equivalent.

Panel Layout

Metallic

NEMA Enclosure

Raceway

 

PE

Filter

 

AC In

Fuses

L2

Bonded to mounting plate

L1

and enclosure wall

External Encoder

 

 

Drive

 

Through wall shield grommets

Customer supplied terminal strip (optional) Connect shield through and to mounting plate

Motor Feedback Cable

Motor Power Cable

Motor

Figure 2: AC Filter and Cable Connections