Emerson 400518-01 Transformer Sizing, Single Phase Power Supply Connections, To Drive Terminals

Models: 400518-01

1 88
Download 88 pages 22.24 Kb
Page 26
Image 26
To Drive

Safety Information

Product Overview

Installation

Diagnostics

Options and

Specification

Accessories

 

 

 

 

 

DISTRIBUTION PANEL

3 Ø Isolation Step Down Transformer

 

 

 

 

 

 

L3

 

 

 

 

 

L2

 

> 140 Vac

 

 

 

 

To Fusing and

 

 

 

 

Drive Terminals

 

 

 

 

L1

 

 

 

 

 

N

 

EARTH

 

 

 

PE

 

GROUND

 

 

(Protective Earth)

 

Figure 12: Grounded WYE Distribution >140 Vac Phase to Neutral. Recommend Using Step Down Transformer so Line to Line is 240 Vac or less.

Fuse

Figure 13: Single Phase Power Supply Connections L1

To Drive

Terminals

Transformer Sizing L2

Fuse

Manual background L1

To Drive

Terminals

Manual background L2

Fuse

Figure 13: Single Phase Power Supply Connections

Transformer Sizing

If your application requires a transformer, use the following table for sizing the KVA rating. The values in the table are based on “worst case” power usage and can be considered a conservative recommendation. You can down-size the values only if the maximum power usage is less than the transformer continuous power rating. Other factors that may influence the required KVA rating are high transformer ambient temperatures (>40° C or >104° F) and drive operation near the maximum speeds.

Transformer output voltage drop may become a limiting factor at motor speeds and loads near maximum ratings. Typically, higher KVA transformers have lower voltage drop due to lower impedance.

14

Page 26
Image 26
Emerson 400518-01 installation manual Transformer Sizing, Single Phase Power Supply Connections, To Drive Terminals