Underwriters Laboratories Listed

LISTED 51Y8

IND. CONT. EQ.

File E 58592 Sec.5

The Epsilon Digital Servo Drives are marked with the “UL Listed” label after passing a rigorous set of design and testing criteria developed by UL (UL508C). This label indicates that UL certifies this product to be safe when installed according to the installation guidelines and used within the product specifications.

The “conditions of acceptability” required by UL are:

Operating within ratings for Input Voltage, Input Current, and Output Current

Rated Output Current (Amps RMS)

Drive Model

Continuous

Peak

(Full Load Amperes)

 

 

 

 

 

EP202

2.2

4.4

 

 

 

EP204

4.0

8.0

 

 

 

EP206

6.5

13.0

 

 

 

Epsilon drive maximum surrounding air temperature 40° C (104° F) at rated Full Load Amperes (FLA)

Epsilon drive maximum surrounding air temperature 50°C (122° F) with output current derated 20% for EP206, 10% for EP204, and no derating required for EP202

Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit protection must be provided in accordance with the National Electrical Code and any additional local codes.

Copper only conductors with 75°C minimum insulation rating at all power and motor terminals

This product is suitable for use on a circuit capable of delivering not more than 10,000 RMS symmetrical amperes, 240 volts maximum, when protected by a Class RK1 or Class CC fuse, rated not more than 15 A

Logic power and I/O power are to be supplied with a UL listed or "recognized component" power supply rated as limited voltage/limited current or limited voltage/limited power

The following warning is presented here and furnished on a label to be placed on the enclosure door

Drive has high fault current rating. The opening of the branch circuit protective device may be an indication that a fault current has been interrupted. All current carrying ports and other components protected by this device should be examined and replaced if damaged. If burn-out of the current element of an overload relay occurs, the complete overload relay must be replaced.

v