Emerson Process Management 1500 4 Status alarms and remedies continued, Troubleshooting, Alarm

Models: 1500

1 146
Download 146 pages 48.94 Kb
Page 104
Image 104
Table 11-4Status alarms and remedies continued

Troubleshooting

Table 11-4Status alarms and remedies continued

Alarm

 

 

code

ProLink II label

Possible remedy

 

 

 

A011

Cal Fail, Too Low

Ensure that there is no flow through the sensor, then retry.

 

 

 

 

 

Cycle power to the flowmeter, then retry.

 

 

 

A012

Cal Fail, Too High

Ensure that there is no flow through the sensor, then retry.

 

 

 

 

 

Cycle power to the flowmeter, then retry.

 

 

 

A013

Cal Fail, Too Noisy

Remove or reduce sources of electromechanical noise, then attempt the

 

 

calibration or zero procedure again.

 

 

Sources of noise include:

 

 

• Mechanical pumps

 

 

• Pipe stress at sensor

 

 

• Electrical interference

 

 

• Vibration effects from nearby machinery

 

 

 

 

 

Cycle power to the flowmeter, then retry. See Section 11.22.

 

 

 

A014

Transmitter Error

Cycle power to the flowmeter.

 

 

 

 

 

The transmitter might need service. Contact Micro Motion. See Section 1.8.

 

 

 

A016

Sensor RTD Error

Check the test points. See Section 11.23.

 

 

 

 

 

Check the sensor coils. See Section 11.25.

 

 

 

 

 

Check wiring to sensor. See Section 11.14.2.

 

 

 

 

 

Make sure the appropriate sensor type is configured. See Section 4.2.

 

 

 

 

 

Contact Micro Motion. See Section 1.8.

 

 

 

A017

Meter RTD Error

Check the test points. See Section 11.23.

 

 

 

 

 

Check the sensor coils. See Section 11.25.

 

 

 

 

 

Contact Micro Motion. See Section 1.8.

 

 

 

A018

EEPROM Failure

Cycle power to the flowmeter.

 

 

 

 

 

The transmitter might need service. Contact Micro Motion. See Section 1.8.

 

 

 

A019

RAM Failure

Cycle power to the flowmeter.

 

 

 

 

 

The transmitter might need service. Contact Micro Motion. See Section 1.8.

 

 

 

A020

Cal Factors Missing

Check the characterization. Specifically, verify the FCF value. See Section 4.2.

 

 

 

A021

Sensor Type Incorrect

Check the characterization. Specifically, verify the K1 value. See Section 4.2.

 

 

 

A022(1)

CP Configuration Failure

Cycle power to the flowmeter.

 

 

 

 

 

The transmitter might need service. Contact Micro Motion. See Section 1.8.

 

 

 

A023(1)

CP Totals Failure

Cycle power to the flowmeter.

 

 

 

 

 

The transmitter might need service. Contact Micro Motion. See Section 1.8.

 

 

 

A024(1)

CP Program Corrupt

Cycle power to the flowmeter.

 

 

 

 

 

The transmitter might need service. Contact Micro Motion. See Section 1.8.

 

 

 

A025(1)

CP Boot Program Fault

Cycle power to the flowmeter.

 

 

 

 

 

The transmitter might need service. Contact Micro Motion. See Section 1.8.

 

 

 

A026

Xmtr Comm Problem

Check the wiring between the transmitter and the core processor (see

Section 11.14.2). The wires may be swapped. After swapping wires, cycle power to the flowmeter.

Check for noise in wiring or transmitter environment.

Check the core processor LED. See Section 11.24.

Check that the core processor is receiving power. See Section 11.14.1.

Perform the core processor resistance test. See Section 11.24.2.

96

Micro Motion® Model 1500 Transmitters with the Filling and Dosing Application

Page 104
Image 104
Emerson Process Management 1500 4 Status alarms and remedies continued, Troubleshooting, Alarm, code, ProLink II label