Troubleshooting
Table 11-2 I/O problems and remedies continued
Symptom | Possible cause | Possible remedy |
|
|
|
mA reading correct at low | mA loop resistance may be too high | Verify that mA output load resistance is below |
currents but wrong at higher |
| maximum supported load (see installation |
currents |
| manual for your transmitter). |
|
|
|
Cannot zero with Zero | Not pressing Zero button for sufficient | Button must be pressed for 0.5 seconds to be |
button | interval | recognized. Press button until LED starts to |
|
| flash yellow, then release button. |
|
|
|
| Core processor in fault mode | Correct core processor faults and retry. |
|
|
|
Cannot connect to terminals | Terminals not in service port mode | Terminals are accessible in service port mode |
33 & 34 in service port mode |
| ONLY for a |
|
| Cycle power and connect during this interval. |
|
|
|
| Leads reversed. | Switch leads and try again. |
|
|
|
| Transmitter installed on multidrop | All Model 1500 and 2500 devices on network |
| network | default to address=111 during |
|
| service port interval. Disconnect or power down |
|
| other devices, or use |
|
|
|
Cannot establish Modbus | Incorrect Modbus configuration | After |
communication on terminals |
| transmitter switches to Modbus |
33 & 34 |
| communications. Default settings are: |
|
| • Address=1 |
|
| • Baud rate=9600 |
|
| • Parity=odd |
|
| Verify configuration. Default settings can be |
|
| changed using ProLink II v2.0 or higher. |
|
|
|
| Leads reversed | Switch leads and try again. |
|
|
|
DI is fixed and does not | Possible internal/external power | Internal means that the transmitter will supply |
respond to input switch | configuration error | power to the output. External means that an |
|
| external |
|
| required. Verify configuration setting is correct |
|
| for desired application. |
|
|
|
11.9Transmitter status LED
The Model 1500 transmitter includes a LED that indicates transmitter status. See Table
1.View the alarm code using ProLink II.
2.Identify the alarm (see Section 11.10).
3.Correct the condition.
Table
Status LED state | Alarm priority | Definition |
|
|
|
Green | No alarm | Normal operating mode |
|
|
|
Flashing yellow | No alarm | Zero in progress |
|
|
|
Yellow | Low severity alarm | • Alarm condition: will not cause measurement error |
|
| • Outputs continue to report process data |
|
| • May indicate that the fill is not completely |
|
| configured |
|
|
|
Red | High severity alarm | • Alarm condition: will cause measurement error |
|
| • Outputs go to configured fault indicators, unless |
|
| the output is configured for valve control |
|
|
|
94 | Micro Motion® Model 1500 Transmitters with the Filling and Dosing Application |