Emerson Process Management 1500 2 I/O problems and remedies continued, 11.9Transmitter status LED

Models: 1500

1 146
Download 146 pages 48.94 Kb
Page 102
Image 102

Troubleshooting

Table 11-2I/O problems and remedies continued

Symptom

Possible cause

Possible remedy

 

 

 

mA reading correct at low

mA loop resistance may be too high

Verify that mA output load resistance is below

currents but wrong at higher

 

maximum supported load (see installation

currents

 

manual for your transmitter).

 

 

 

Cannot zero with Zero

Not pressing Zero button for sufficient

Button must be pressed for 0.5 seconds to be

button

interval

recognized. Press button until LED starts to

 

 

flash yellow, then release button.

 

 

 

 

Core processor in fault mode

Correct core processor faults and retry.

 

 

 

Cannot connect to terminals

Terminals not in service port mode

Terminals are accessible in service port mode

33 & 34 in service port mode

 

ONLY for a 10-second interval after power-up.

 

 

Cycle power and connect during this interval.

 

 

 

 

Leads reversed.

Switch leads and try again.

 

 

 

 

Transmitter installed on multidrop

All Model 1500 and 2500 devices on network

 

network

default to address=111 during 10-second

 

 

service port interval. Disconnect or power down

 

 

other devices, or use RS-485 communications.

 

 

 

Cannot establish Modbus

Incorrect Modbus configuration

After 10-second interval on power-up, the

communication on terminals

 

transmitter switches to Modbus

33 & 34

 

communications. Default settings are:

 

 

• Address=1

 

 

• Baud rate=9600

 

 

• Parity=odd

 

 

Verify configuration. Default settings can be

 

 

changed using ProLink II v2.0 or higher.

 

 

 

 

Leads reversed

Switch leads and try again.

 

 

 

DI is fixed and does not

Possible internal/external power

Internal means that the transmitter will supply

respond to input switch

configuration error

power to the output. External means that an

 

 

external pull-up resistor and source are

 

 

required. Verify configuration setting is correct

 

 

for desired application.

 

 

 

11.9Transmitter status LED

The Model 1500 transmitter includes a LED that indicates transmitter status. See Table 11-3. If the status LED indicates an alarm condition:

1.View the alarm code using ProLink II.

2.Identify the alarm (see Section 11.10).

3.Correct the condition.

Table 11-3Model 1500/2500 transmitter status reported by the status LED

Status LED state

Alarm priority

Definition

 

 

 

Green

No alarm

Normal operating mode

 

 

 

Flashing yellow

No alarm

Zero in progress

 

 

 

Yellow

Low severity alarm

• Alarm condition: will not cause measurement error

 

 

• Outputs continue to report process data

 

 

• May indicate that the fill is not completely

 

 

configured

 

 

 

Red

High severity alarm

• Alarm condition: will cause measurement error

 

 

• Outputs go to configured fault indicators, unless

 

 

the output is configured for valve control

 

 

 

94

Micro Motion® Model 1500 Transmitters with the Filling and Dosing Application

Page 102
Image 102
Emerson Process Management 1500 manual 2 I/O problems and remedies continued, 11.9Transmitter status LED, Troubleshooting