Configuring the Filling and Dosing Application
Figure 7-5 Analog Output panel
5.If you want to use overshoot compensation, see Section 7.5 for options and configuration instructions. This applies to both fixed and automatic overshoot compensation (AOC).
6.If Channel C has been configured as a discrete input, you can assign a fill control function to this channel. See Section 8.3.2.
7.4.1Flow source
The flow source specifies the flow variable that will be used to measure fill quantity. Select one of the flow sources defined in Table
•If you select None, the filling application is automatically disabled.
•If you select Mass Flow Rate or Volume Flow Rate, that variable will automatically be defined as the 100 Hz variable, and Update Rate will automatically be set to Special. See Section 6.7 for more information.
Note: If the filling application is enabled, you should not specify any variable other than the flow source variable as the 100 Hz variable.