Required Transmitter Configuration
4.3Configuring the channels
The six input/output terminals provided on the Model 1500 are organized into three pairs. These pairs are called Channels A, B, and C. The channels should be configured before doing any other I/O configuration.
CAUTION
Changing the channel configuration without verifying I/O configuration can produce process error.
When the configuration of a channel is changed, the channel’s behavior will be controlled by the I/O configuration that is stored for the new channel type, which may or may not be appropriate for the process. To avoid causing process error:
•Configure the channels before configuring the I/O.
•When changing channel configuration, be sure that all control loops affected by this channel are under manual control.
•Before returning the loop to automatic control, ensure that the channel's I/O is correctly configured for your process. See Sections 4.5, 4.6, and 4.7.
The outputs and variable assignments are controlled by the channel configuration. Table
.
Table 4-2 Channel configuration options
Channel | Terminals | Configuration Option | Power |
|
|
|
|
A | 21 & 22 | mA output (not configurable) | Internal (not configurable) |
|
|
|
|
B | 23 & 24 | Discrete output 1 (DO1) | Internal or external(1) |
|
|
|
|
C | 31 & 32 | Discrete output 2 (DO2) | Internal or external(1) |
|
|
|
|
|
| Discrete input (DI) |
|
|
|
|
|
(1) If set to external power, you must provide power to the outputs.
To configure the channels, see the menu flowchart in Figure
Figure 4-5 Configuring the channels
ProLink Menu
Configuration
Channel
Channel B
·Type assignment
·Power type
Channel C
·Type assignment
·Power type
Before You Begin
Using ProLink II
Flowmeter Startup
Required Configuration
Configuration and Use Manual | 19 |