Optional Transmitter Configuration

If the transmitter detects slug flow:

A slug flow alarm is posted immediately.

During the slug duration period, the transmitter holds the mass flow rate at the last measured pre-slug value, independent of the mass flow rate measured by the sensor. All outputs that report mass flow rate and all internal calculations that include mass flow rate will use this value.

If slugs are still present after the slug duration period expires, the transmitter forces the mass flow rate to 0, independent of the mass flow rate measured by the sensor. All outputs that report mass flow rate and all internal calculations that include mass flow rate will use 0.

When process density returns to a value within the slug flow limits, the slug flow alarm is cleared and the mass flow rate reverts to the actual measured value.

Note: Raising the low slug flow limit or lowering the high slug flow limit will increase the possibility that the transmitter will report slug flow.

Note: The slug flow limits must be entered in g/cm3, even if another unit has been configured for density. Slug flow duration is entered in seconds.

Note: If slug flow duration is set to 0, the mass flow rate will be forced to 0 as soon as slug flow is detected.

6.11Configuring fault handling

There are four ways that the transmitter can report faults:

By setting the mA output to its configured fault level (see Section 4.5.4 )

By configuring a discrete output to indicate fault status (see Section 4.6)

By setting the digital communications fault indicator (see Section 6.12.1)

By posting an alarm to the active alarm log

Status alarm severity controls which of these methods is used. For some faults only, fault timeout controls when the fault is reported.

6.11.1Changing status alarm severity

Status alarms are classified into three levels of severity. Severity level controls transmitter behavior when the alarm condition occurs. See Table 6-4.

Table 6-4Alarm severity levels

Severity level

Transmitter action

 

 

Fault

If this condition occurs, an alarm will be generated and all outputs go to their

 

configured fault levels. Output configuration is described in Chapter 4.

 

 

Informational

If this condition occurs, an alarm will be generated but output levels are not affected.

 

 

Ignore

If this condition occurs, no alarm will be generated (no entry is added to the active

 

alarm log) and output levels are not affected.

 

 

You cannot reclassify a Fault alarm, or change another alarm to a Fault alarm. However, alarms can be reclassified from Informational to Ignore, or vice versa. For example, the default severity level for the A118 – DO1 Fixed alarm is Information, but you can set it to Ignore.

Using the Transmitter

Optional Configuration

Filler Configuration

Using the Filler

Configuration and Use Manual

47

Page 55
Image 55
Emerson Process Management 1500 manual Configuring fault handling, Changing status alarm severity, 4Alarm severity levels

1500 specifications

Emerson Process Management 1500 is a cutting-edge distributed control system designed to enhance operational efficiency, safety, and reliability in industrial processes. Renowned for its robust architecture and scalable features, the 1500 system caters to various sectors, including oil and gas, pharmaceuticals, chemicals, and utilities.

One of the standout features of the Emerson 1500 is its modular design, allowing users to customize and scale the system according to their specific needs. This flexibility ensures that operations can grow and adapt without requiring a complete system overhaul. The control system supports a range of I/O modules, enabling integration with various field devices and technologies.

The Emerson 1500 employs advanced control algorithms to optimize process performance. This includes model predictive control (MPC) and multivariable control, which enhance the ability to manage complex processes through predictive analytics. This predictive capability not only improves operational efficiency but also reduces downtime and maintenance costs.

In addition to its advanced control features, the 1500 system is known for its user-friendly interface. Operators can easily navigate the system through intuitive graphics and dashboards, allowing them to monitor processes in real time. This ease of use significantly reduces training time and improves response times during operational changes or emergencies.

Security is a critical concern for modern industrial control systems, and the Emerson 1500 addresses this with a multi-layered security framework. This includes secure communications, robust authentication, and access controls, ensuring that only authorized personnel can interact with the system.

The Emerson Process Management 1500 also emphasizes interoperability, supporting various communication protocols such as Ethernet/IP, Modbus, and HART, facilitating seamless integration with existing infrastructure. This capability is particularly advantageous for organizations looking to modernize their systems without entirely replacing legacy equipment.

Furthermore, the system supports advanced data analytics and cloud connectivity, allowing organizations to leverage big data for predictive maintenance, performance benchmarking, and decision-making processes. By harnessing the power of data, users can achieve greater efficiencies and drive continuous improvement across their operations.

In summary, the Emerson Process Management 1500 is a versatile and advanced distributed control system characterized by modularity, advanced control features, user-friendliness, robust security, interoperability, and data analytics capabilities. Its comprehensive approach ensures that industries can not only meet current operational demands but also prepare for future challenges in an ever-evolving landscape.