Emerson Process Management 1500 manual 6.11.2Changing the fault timeout

Models: 1500

1 146
Download 146 pages 48.94 Kb
Page 57
Image 57
6.11.2Changing the fault timeout

Optional Transmitter Configuration

Table 6-5Status alarms and severity levels continued

 

 

Default

 

Affected by

Alarm code

ProLink II message

severity

Configurable?

fault timeout?

 

 

 

 

 

A118

DO1 Fixed

Info

Yes

No

 

 

 

 

 

A119

DO2 Fixed

Info

Yes

No

 

 

 

 

 

A131(2)

Meter Verification/Outputs at Last Value

Info

Yes

No

 

 

 

 

 

(1)Applies only to systems with the standard core processor.

(2)Applies only to systems with the enhanced core processor.

6.11.2Changing the fault timeout

By default, the transmitter immediately reports a fault when a fault is encountered. For specific faults, you can configure the transmitter to delay reporting the fault by changing the fault timeout to a non-zero value. If fault timeout is configured:

During the fault timeout period, the transmitter continues to report its last valid measurement.

The fault timeout applies only to the mA output and discrete output. Fault indication via digital communications is unaffected.

The fault timeout is not applicable to all faults. See Table 6-5 for information about which faults are affected by fault timeout.

6.12Configuring digital communications

The digital communications parameters control how the transmitter will communicate using Modbus/RS-485 protocol.

The following digital communications parameters can be configured:

Fault indicator

Modbus address

RS-485 settings

Floating-point byte order

Additional communications response delay

6.12.1Changing the digital communications fault indicator

The transmitter can indicate fault conditions using a digital communications fault indicator. Table 6-6lists the options for the digital communications fault indicator.

Note: If an output is configured for valve control, the output will never go to fault levels.

Table 6-6Digital communications fault indicators and values

Fault indicator options

Fault output value

 

 

Upscale

Process variables indicate the value is greater than the upper sensor limit. Totalizers

 

stop counting.

 

 

Downscale

Process variables indicate the value is less than the lower sensor limit. Totalizers stop

 

counting.

 

 

Zero

Flow rates go to the value that represents zero flow, and density and temperature

 

values are reported as zero. Totalizers stop counting.

 

 

Using the Transmitter

Optional Configuration

Filler Configuration

Using the Filler

Configuration and Use Manual

49

Page 57
Image 57
Emerson Process Management 1500 manual 6.11.2Changing the fault timeout, 6.12Configuring digital communications