Configuring the Filling and Dosing Application
Table
Flow option | Default | Description |
|
|
|
Open Primary | 0.00% of target | Enter the quantity or the percent of the target at which the primary valve will |
|
| open. |
|
| Either Open Primary or Open Secondary must be set to 0. If one of these |
|
| parameters is set to a |
|
| Before a fill of this type can be started, the primary valve must be assigned to |
|
| a discrete output. See Section 7.4, Step 4. |
|
|
|
Open | 0.00% of target | Enter the quantity or the percent of the target at which the secondary valve will |
Secondary |
| open. |
|
| Either Open Primary or Open Secondary must be set to 0. If one of these |
|
| parameters is set to a |
|
| Before a fill of this type can be started, the secondary valve must be assigned |
|
| to a discrete output. See Section 7.4, Step 4. |
|
|
|
Close Primary | 100.00% of target | Enter the percent of the target, or the quantity to be subtracted from the target, |
|
| at which the primary valve will close.(1) |
|
| Either Close Primary or Close Secondary must be set to close when the target |
|
| is reached. If one of these parameters is set to a value that is not the target, |
|
| the other is adjusted accordingly. |
|
|
|
Close | 100.00% of target | Enter the percent of the target, or the quantity to be subtracted from the target, |
Secondary |
| at which the secondary valve will close.(1) |
|
| Either Close Primary or Close Secondary must be set to close when the target |
|
| is reached. If one of these parameters is set to a value that is not the target, |
|
| the other is adjusted accordinly. |
(1) See the definition of Configure By in Table
Table
Flow option | Default | Description |
|
|
|
Open Full | 0.00% of target | Enter the quantity or the percent of the target at which the valve will transition |
|
| from partial flow to full flow. |
|
|
|
Close Partial | 100.00% of target | Enter the percent of the target, or the quantity to be subtracted from the target, |
|
| at which the valve will transition from full flow to partial flow.(1) |
(1) See the definition of Configure By in Table
7.5Overshoot compensation
Overshoot compensation keeps the actual quantity delivered as close as possible to the fill target by compensating for the time required to close the valve. Without overshoot compensation, there will always be some amount of overfill because of the time required for the transmitter to observe that the target has been reached and send the command to close the valve, and then for the control system and valve to respond. When overshoot compensation is configured, the transmitter issues the valve close command before the target is reached. See Figure
62 | Micro Motion® Model 1500 Transmitters with the Filling and Dosing Application |