Troubleshooting
Some fault conditions can be corrected by cycling power to the transmitter. A power cycle can clear the following:
•Loop test
•Zero failure
•Stopped internal totalizer
11.8I/O problems
If you are experiencing problems with an mA output, discrete output, or discrete input, use Table
Table 11-2 I/O problems and remedies
Symptom | Possible cause | Possible remedy | |
|
|
| |
No output | Power supply problem | Check power supply and power supply wiring. | |
Loop test failed |
| See Section 11.14.1. | |
|
|
| |
| Fault condition present if fault | Check the fault indicator settings to verify | |
| indicators are set to downscale or | whether or not the transmitter is in a fault | |
| internal zero | condition. See Section 4.5.4 to check the mA | |
|
| fault indicator. | |
|
| If a fault condition is present, see Section 11.7. | |
|
|
| |
| Channel not configured for desired | Verify channel configuration for associated | |
| output (Channel B or C only) | output terminals. | |
|
|
| |
mA output < 4 mA | Process condition below LRV | Verify process. | |
|
| Change the LRV. See Section 4.5.2. | |
|
|
| |
| Fault condition if fault indicator is set to | Check the fault indicator settings to verify | |
| internal zero | whether or not the transmitter is in a fault | |
|
| condition. See Section 4.5.4. | |
|
| If a fault condition is present, see Section 11.7. | |
|
|
| |
| Open in wiring | Verify all connections. | |
|
|
| |
| Channel not configured for mA | Verify channel configuration. | |
| operation |
| |
|
|
| |
| Bad mA receiving device | Check the mA receiving device or try another | |
|
| mA receiving device. See Section 11.16. | |
|
|
| |
| Bad output circuit | Measure DC voltage across output to verify that | |
|
| output is active. | |
|
|
| |
Constant mA output | Output is fixed in a test mode | Exit output from test mode. See Section 3.3. | |
|
|
| |
| Zero calibration failure | Cycle power. | |
|
| Stop flow and rezero. See Section 3.5. | |
|
|
| |
mA output consistently out of | Fault condition if fault indicator is set to | Check the fault indicator settings to verify | |
range | upscale or downscale | whether or not the transmitter is in a fault | |
|
| condition. See Section 4.5.4. | |
|
| If a fault condition is present, see Section 11.7. | |
|
|
| |
| LRV and URV not set correctly | Check the LRV and URV. See Section 11.20. | |
|
|
| |
Consistently incorrect mA | Output not trimmed correctly | Trim the output. See Section 3.4. | |
measurement |
|
| |
Incorrect flow measurement unit | Verify flow measurement unit configuration. See | ||
| |||
| configured | Section 11.19. | |
|
|
| |
| Incorrect process variable configured | Verify process variable assigned to mA output. | |
|
| See Section 4.5.1. | |
|
|
| |
| LRV and URV not set correctly | Check the LRV and URV. See Section 11.20. | |
|
|
|