Configuring the Filling and Dosing Application
Table 7-3 Filling control options continued
Control option | Default | Description |
|
|
|
Purge Time | 1.00000 sec | Used only if Purge Mode is set to Auto. |
|
| Enter the purge duration, in seconds. When Purge Time has elapsed, the purge |
|
| (secondary) valve will be closed automatically. |
|
|
|
AOC Algorithm | Underfill | Select the type of overshoot compensation to be performed: |
|
| • Underfill – The actual quantity delivered will never exceed the target quantity. |
|
| • Overfill – The actual quantity delivered will never be less than the target |
|
| quantity. |
|
| • Fixed – The valve will close at the point defined by the target quantity minus |
|
| the Fixed Overshoot Comp parameter. |
|
| Underfill and Overfill are available only if AOC is enabled. |
|
| Fixed is available only if AOC is disabled. |
|
|
|
AOC Window | 10 | For standard AOC calibration, specify the maximum number of fills that will be |
Length |
| run during calibration. |
|
| For rolling AOC calibration, specify the number of fills that will be used to |
|
| calculate AOC. |
|
|
|
Fixed Overshoot | 0.00000 | Used only if AOC is disabled and AOC Algorithm is set to Fixed. |
Comp |
| Enter the value to be subtracted from the target quantity to determine the point |
|
| at which the valve will close. Enter the value in mass or volume units, as |
|
| appropriate to the configured flow source. |
|
|
|
7.4.3Valve control parameters
The valve control parameters are used to open and close the valves at particular points in the fill process.
•Valve control parameters for
•Valve control parameters for
Note: Valve control parameters are not used for
Using the Transmitter
Optional Configuration
Filler Configuration
Using the Filler
Configuration and Use Manual | 61 |