Errors

Error messages that may be displayed on the Integral Display, on a 375

 

Handheld Communicator, in AMS, or in RRM are shown in Table 7-5.Errors

 

normally result in Analog Output alarm.

 

Errors are indicated in RRM in the Diagnostics window.

Table 7-5. Error messages.

Message

Description

 

Action

RAM error

An error in the gauge data memory

Contact Emerson Process

 

(RAM) has been detected during the

Management Service Department.

 

startup tests. Note: this automatically

 

 

 

resets the gauge.

 

 

FPROM error

An error in the gauge program

Contact Emerson Process

 

memory (FPROM) has been detected

Management Service Department.

 

during the startup tests. Note: this

 

 

 

automatically resets the gauge.

 

 

Database (Hreg) error

An error in the transmitter

Load default database and restart the

 

configuration memory (EEPROM) has

transmitter. Contact Emerson

 

been detected. The error is either a

Process Management Service

 

checksum error that can be solved by

Department if the problem persists.

 

loading the default database or a

 

 

 

hardware error.

 

 

 

NOTE: the default values are used

 

 

 

until the problem is solved.

 

 

Microwave Module error

An error in the microwave module.

Contact Emerson Process

 

 

Management Service Department.

LCD error

An error in the LCD is detected.

Contact Emerson Process

 

 

Management Service Department.

Modem error

An error in the modem used for digital

Contact Emerson Process

 

communication has been detected.

Management Service Department.

Analog out error

An error in the Analog Out Module.

Contact Emerson Process

 

 

Management Service Department.

Internal temperature error

An error in the internal temperature

Contact Emerson Process

 

measurement.

Management Service Department.

 

-40 ºC<Internal Temperature<85 ºC.

 

 

Other hardware error

An unspecified hardware error has

Contact Emerson Process

 

been detected.

Management Service Department.

Measurement error

A serious measurement error has

Contact Emerson Process

 

been detected.

Management Service Department.

Configuration error

At least one configuration parameter

Load the default database and

 

is outside allowed range.

 

restart the transmitter (see “Reset

 

NOTE: the default values are used

 

to Factory Settings” on page 7-22)

 

until the problem is solved.

Configure the transmitter or upload

 

 

 

a backup configuration file (see

 

 

 

“Backing up the Transmitter

 

 

 

Configuration” on page 7-20)

 

 

• Contact Emerson Process

 

 

 

Management Service Department if

 

 

 

the problem persists

 

 

 

Software error

An error has been detected in the

Contact Emerson Process

 

transmitter software.

Management Service Department.