Emerson Process Management 5300 manual Block Errors, Modes, Table J-2. Blockerr Conditions

Models: 5300

1 324
Download 324 pages 46.88 Kb
Page 312
Image 312

Rosemount 5300 Series

Reference Manual

00809-0100-4530, Rev BA July 2009

BLOCK ERRORS

Table J-2lists conditions reported in the BLOCK_ERR parameter.

Table J-2. BLOCK_ERR

 

 

Conditions

Condition

Condition Name and Description

 

Number

 

 

 

 

 

 

0

Other

 

1

Block Configuration Error: the selected channel carries a measurement that

 

 

is incompatible with the engineering units selected in XD_SCALE, the

 

 

L_TYPE parameter is not configured, or CHANNEL = zero.

 

2

Link Configuration Error

 

3

Simulate Active: Simulation is enabled and the block is using a simulated

 

 

value in its execution.

 

4

Local Override

 

5

Device Fault State Set

 

6

Device Needs Maintenance Soon

 

7

Input Failure/Process Variable has Bad Status: The hardware is bad, or a

 

 

bad status is being simulated.

 

8

Output Failure: The output is bad based primarily upon a bad input.

 

9

Memory Failure

 

10

Lost Static Data

 

11

Lost NV Data

 

12

Readback Check Failed

 

13

Device Needs Maintenance Now

 

14

Power Up

 

15

Out of Service: The actual mode is out of service.

MODES

The AI Function Block supports three modes of operation as defined by the

MODE_BLK parameter:

Manual (Man) The block output (OUT) may be set manually

Automatic (Auto) OUT reflects the analog input measurement or the simulated value when simulation is enabled

Out of Service (O/S) The block is not processed. FIELD_VAL and PV are not updated and the OUT status is set to Bad: Out of Service. The BLOCK_ERR parameter shows Out of Service. In this mode, you can make changes to all configurable parameters. The target mode of a block may be restricted to one or more of the supported modes.

J-6

Page 312
Image 312
Emerson Process Management 5300 manual Block Errors, Modes, Table J-2. Blockerr Conditions