Reference Manual

00809-0100-4530, Rev BA July 2009

Rosemount 5300 Series

DIAGNOSTIC

MESSAGES

Troubleshooting

If there is a malfunction despite the absence of diagnostic messages, see

 

 

Table 7-3for information on possible causes.

Table 7-3. Troubleshooting

 

 

 

 

 

chart

 

 

 

 

 

 

 

 

 

 

 

 

 

Symptom

 

 

Possible cause

 

Action

 

No level reading

 

Power disconnected

Check the power supply

 

 

 

Data communication cables

Check the cables for serial data

 

 

 

 

disconnected

 

communication

 

 

 

Probe is not connected

View the Diagnostic window, see

 

 

 

 

 

 

“Diagnostics” on page 7-23 in order to

 

 

 

 

 

 

check active status messages

 

 

 

 

 

Check if “Probe Missing” is active. If it is,

 

 

 

 

 

 

check the probe connection

 

 

 

 

 

 

No HART communication.

 

• COM Port configuration does not match

• Check that correct COM Port is selected in

 

 

 

 

the connected COM Port

 

the HART server (see “Specifying the COM

 

 

 

• Cables may be disconnected

 

Port” on page 5-15

 

 

 

• Wrong HART address is used

• Check wiring diagram

 

 

 

Hardware failure

Verify that the 250 Ω resistor is in the loop.

 

 

 

HART resistor

Check cables

 

 

 

 

 

Make sure that correct HART short address

 

 

 

 

 

 

is used. Try address=0

 

 

 

 

 

Check Analog Output current value to verify

 

 

 

 

 

 

that transmitter hardware works

 

 

 

 

 

Check that the correct settings are used in

 

 

 

 

 

 

RRM. Select Device, Search from the

 

 

 

 

 

 

menu. Click Settings and HART tab. Make

 

 

 

 

 

 

sure the values are properly chosen. The

 

 

 

 

 

 

standard values are shown on page 5-10

 

Analog Out is set in Alarm.

 

Measurement or transmitter failure.

View the Diagnostic window, see

 

 

 

 

 

“Diagnostics” on page 7-23to check active

 

 

 

 

 

error and status messages.

 

Both Surface pulse and Interface

 

Measurement Mode is set to “Level Only”.

Set Measurement Mode to “Level and

 

Pulse are detected, but Interface

 

 

 

Interface” (see “Basic Configuration

 

Level is reported as unknown in the

 

 

Parameters” on page 5-4).

 

Echo Curve plot.

 

 

 

 

 

 

Both Surface pulse and Interface

 

Interface pulse is identified as a double

No action required. Use the Echo Curve plot

 

pulse are detected, but Interface

 

 

bounce

to verify that the surface and interface are

 

Level is reported as unknown in the

Surface pulse and Interface pulse are

close, see “Analyzing the Measurement

 

Echo Curve plot.

 

 

very close

Signal” on page 7-3.

 

 

 

 

 

 

Surface pulse is detected, but Level is

Wrong Probe Type set

View the Diagnostics window, see

 

incorrectly reported as Full or Empty.

Bad Reference Threshold value

“Diagnostics” on page 7-23,to check active

 

 

 

 

 

messages and check if the warning “Full

 

 

 

 

 

Tank/Empty Tank” is active. If this is the case,

 

 

 

 

 

check that:

 

 

 

 

 

the transmitter is configured with correct

 

 

 

 

 

 

probe type

 

 

 

 

 

the reference pulse is below the reference

 

 

 

 

 

 

amplitude threshold. If not, adjust

 

 

 

 

 

 

reference threshold to an appropriate

 

 

 

 

 

 

value

7-33