Rosemount 5300 Series

Reference Manual

00809-0100-4530, Rev BA July 2009

Table I-1.

RB.RECOMMENDED_ACTION

PlantWeb Alerts

 

Alarm Type

 

Failed/Maint/Advise

 

Recommended Action

 

 

Active Event

 

Text String

 

None

 

None

 

No action required

 

 

 

 

 

 

Non-Volatile Writes Deferred

 

Non-volatile writes have been deferred, leave

 

 

 

 

 

the device powered until the advisory goes

 

 

 

 

 

away.

 

Advisory

 

Electronics Warning -

 

Check device installation and configuration

 

 

 

Transducer Block

 

 

 

 

 

 

PlantWeb Alerts Simulation

 

Use the switch on the Fieldbus electronics

 

 

 

 

 

board to turn simulation on or off.

 

 

 

Probe Contamination

 

Clean the probe.

 

 

 

Configuration Error

 

Load default database to the device and

 

 

 

 

 

reconfigure it.

 

 

 

Configuration Warning

 

Check device configuration

 

 

 

Simulation Mode

 

Use Start / Stop Device Simulation to enable

 

 

 

 

 

or disable simulation.

 

Maintenance

 

Vapor Compensation

 

1. Recalibrate vapor compensation.

 

 

Warning

 

2. Check Vapor DC configuration.

 

 

 

 

 

3. Check that the correct probe is attached.

 

 

 

Volume/Temperature

 

1. Check volume configuration.

 

 

 

Measurement Warning

 

2. Check ambient temperature at installation

 

 

 

 

 

 

site.

 

 

 

 

 

3. If the surrounding temperature is OK, it

 

 

 

 

 

 

might indicate a hardware error producing

 

 

 

 

 

 

heat. Replace the transmitter head.

 

 

 

Level / Interface

 

1.

Analyze echo curve for reason and check

 

 

 

Measurement Failure

 

 

device configuration.

 

 

 

 

 

2.

Check device physical installation

 

 

 

 

 

 

(for instance probe contamination).

 

 

 

 

 

3.

Load default database to the device and

 

 

 

 

 

 

reconfigure it.

 

 

 

 

 

4.

If error persists, it might indicate a hardware

 

 

 

 

 

 

error. Replace the transmitter head.

 

 

 

Volume / Temperature

 

1.

If Level Measurement Failure is active, clear

 

 

 

Measurement Failure

 

 

that alert first.

 

 

 

 

 

2.

Check volume configuration.

 

 

 

 

 

3.

Load default database to the device and

 

 

 

 

 

 

reconfigure it.

 

Failed

 

 

 

4. Check ambient temperature at installation site.

 

 

 

 

5.

If error persists, it might indicate a hardware

 

 

 

 

 

 

 

 

 

 

 

error. Replace the transmitter head.

 

 

 

Electronics Failure -

 

Replace transmitter head.

 

 

 

Transducer Block

 

 

 

 

 

 

Probe Missing

 

Check that the probe is properly connected.

 

 

 

Input / Output Failure

 

Replace the transmitter.

 

 

 

Non-Volatile Memory Failure

 

1.

Load default database to the device to clear

 

 

 

 

 

 

the error.

 

 

 

 

 

2.

Download a device configuration.

 

 

 

 

 

3.

If error persists, it may indicate a faulty

 

 

 

 

 

 

memory chip. Replace the transmitter head.

 

 

 

Electronics Failure - Output

 

Replace the transmitter.

 

 

 

Board

 

 

 

 

 

 

Software Incompatible Error

 

Replace the device.

I-8