Reference Manual
00809-0100-4530, Rev BA
July 2009
F-9
Rosemount 5300 Series
DIAGNOSTICS DEVICE
ERRORS In addition to the BLOCK_ERR and XD_ERROR parameters, more detailed

information on the measurement status can be obtained via

DIAGN_DEV_ALERT. TableF-17 lists the potential errors and the possible

corrective actions for the given values. The corrective actions are in order of

increasing system level compromises. The first step should always be to reset

the gauge and then if the error persists, try the steps in TableF-17. Start with

the first corrective action and then try the second.

Table F-17. Device Errors

Diagnostics

Bit Number Value of
DIAGN_DEV_ALERT Description Corrective action
0No alarm active
0 0x00000001 Reserved
10x00000002 FF card to gauge comm fault Replace gauge
2 0x00000004 Level Measurement Failure Verify device installation and configuration
30x00000008 Temperature Measurement
Failure Check ambient temperature. If ambient
temperature ok replace the device.
4 0x00000010 Volume measurement failure Check volume configuration
50x00000020 Database Error Load default database to the device and
reconfigure the device
6 0x00000040 HW Error Replace device
70x00000080 Microwave Unit Error Replace device
8 0x00000100 Configuration Error Load default database to the device and
reconfigure the device
90x00000200 SW Error Replace device
10 0x00000400 Invalid Strap Table Check the Strapping Table configuration
11 0x00000800 Internal Temp Warning Check ambient temperature at installation site
12 0x00001000 Database Warning Check the device configuration
13 0x00002000 HW Warning Check device installation and configuration
14 0x00004000 Microwave Unit Warning Check device installation and configuration
15 0x00008000 Configuration Warning Check the device configuration
16 0x00010000 SW Warning Check device installation and configuration
17 0x00020000 Simulation Mode Use Simulation Method under advanced
configuration tool to get the device out of
Simulation Mode
18 0x00040000 Volume Range Warning Verify Strapping Table
19 0x00080000 Software Write Protected
20 0x00100000 Vapor Compensation Not
Calibrated
21 0x00200000 Vapor DC Estimation Limited
22 0x00400000 Reference Reflector Not
Found
23 0x00800000 BaseLine too low
24 0x01000000 BaseLine too high
25 0x02000000 Gain control
26 0x04000000 Unsupported Combination of
Functions
27 0x08000000
28 0x10000000
29 0x20000000 Probe Missing Check probe connection
30 0x40000000 Interface Measurement
Failure Check interface measurement configuration
31 0x80000000 Hardware Write Protected