Rosemount 5300 Series

Reference Manual

00809-0100-4530, Rev BA July 2009

Geometry

6. Geometry

HART command: [2, 1, 3].

FOUNDATION Fieldbus parameter:

TRANSDUCER 1100>GEOM_TANK_HEIGHT TRANSDUCER 1100>MOUNTING_TYPE TRANSDUCER 1100>PIPE_DIAMETER TRANSDUCER 1100>NOZZLE_HEIGHT

Tank Height is the distance from the Upper Reference Point to the Lower Reference Point (see Figure 5-1 on page 5-4and Figure 5-2 on page 5-4). The Upper Reference Point is located at the bottom part of the threaded adapter, or at the underside of the welded flange.

Make sure the Tank Height is as accurate as possible, since a Tank Height error results in a corresponding Level value offset error.

When specifying the Tank Height, keep in mind that this value is used for all level and volume measurements performed by the Rosemount 5300 Series transmitter.

The Tank Height must be set in linear (level) units, such as feet or meters, regardless of primary variable assignment.

Select the Mounting Type used.

Select Inner Diameter if using pipe, chamber or nozzle. Type Nozzle Height if using nozzle.