Rosemount 5300 Series

Reference Manual

00809-0100-4530, Rev BA July 2009

Channel Definitions

Each input has an assigned channel which can be linked to the AI block. The

 

 

channels for the Rosemount 5300 Series are the following:

Table F-1. Channel

 

 

 

Assignments

 

 

 

 

 

 

 

 

 

Channel Name

 

Channel

Process variable

 

 

Number

 

 

 

 

 

Level

 

1

CHANNEL_RADAR_LEVEL

 

Ullage

 

2

CHANNEL_RADAR_ULLAGE

 

Level Rate

 

3

CHANNEL_RADAR_LEVELRATE

 

Signal Strength

 

4

CHANNEL_RADAR_SIGNAL_STRENGTH

 

Volume

 

5

CHANNEL_RADAR_VOLUME

 

Internal Temperature

 

6

CHANNEL_RADAR_INTERNAL_TEMPERATURE

 

Upper Product Volume

 

7

CHANNEL_UPPER_PRODUCT_VOLUME

 

Lower Product Volume

 

8

CHANNEL_LOWER_ PRODUCT_VOLUME

 

Interface Distance

 

9

CHANNEL_INTERFACE_ DISTANCE

 

Upper Product Thickness

 

10

CHANNEL_UPPER_ PRODUCT_THICKNESS

 

Interface Level

 

11

CHANNEL_INTERFACE_LEVEL

 

Interface Level Rate

 

12

CHANNEL_INTERFACE_ LEVELRATE

 

Interface Signal Strength

 

13

CHANNEL_INTERFACE_ SIGNALSTRENGTH

 

Signal Quality

 

14

CHANNEL_SIGNAL_QUALITY

 

Surface/Noise Margin

 

15

CHANNEL_ SURFACE_NOISE_MARGIN

 

Vapor DC

 

16

CHANNEL_VAPOR_DC

PARAMETERS AND

 

 

 

DESCRIPTIONS

 

 

 

Table F-2. Level Transducer

 

 

 

Block Parameters and

 

 

 

Descriptions.

 

 

 

 

 

 

 

 

 

Parameter

 

Index Number

Description

 

 

 

 

 

 

ST_REV

 

1

The revision level of the static data associated with the

 

 

 

 

function block. The revision value increments each time a

 

 

 

 

static parameter value in the block is changed.

 

TAG_DESC

 

2

The user description of the intended application of the block.

 

STRATEGY

 

3

The strategy field can be used to identify grouping of blocks.

 

 

 

 

This data is not checked or processed by the block.

 

ALERT_KEY

 

4

The identification number of the plant unit. This information

 

 

 

 

may be used in the host for sorting alarms, etc.

 

MODE_BLK

 

5

The actual, target, permitted, and normal modes of the block.

 

 

 

 

Target: The mode to “go to”

 

 

 

 

Actual: The mode the “block is currently in”

 

 

 

 

Permitted: Allowed modes that target may take on

 

 

 

 

Normal: Most common mode for target

 

BLOCK_ERR

 

6

This parameter reflects the error status associated with the

 

 

 

 

hardware or software components associated with a block. It

 

 

 

 

is a bit string, so that multiple errors may be shown.

 

UPDATE_EVT

 

7

This alert is generated by any change to the static data.

F-2

Page 282
Image 282
Emerson Process Management 5300 manual Channel Definitions, Parameters Descriptions, Table F-1. Channel Assignments