Symptom

 

Possible cause

 

Action

The reference pulse is not detected.

•

The tank is full

•

Check the product level

 

•

The transmitter is configured with

•

Check that correct probe type is configured

 

 

wrong probe type

• Check Reference Amplitude Threshold

 

•

Reference Amplitude Threshold is

 

 

 

 

incorrect

 

 

 

 

 

 

 

Incorrect Interface Level reading.

•

Interface threshold incorrect

•

Adjust Interface threshold, see “Interface

 

•

Upper Product Dielectric constant

 

Pulse not Found” on page 7-8

 

 

incorrect

•

Check the Upper Product Dielectric

 

 

 

 

constant, see “Basic Configuration

 

 

 

 

Parameters” on page 5-4

Incorrect level reading.

•

Configuration error

•

Check the Tank Height parameter

 

•

Disturbing objects in the tank

•

Check status information and diagnostic

 

 

 

 

information

 

 

 

•

Check that the transmitter has not locked

 

 

 

 

on an interfering object, see “Disturbance

 

 

 

 

Echo Handling” on page 7-7

 

 

 

• Adjust the Surface amplitude threshold, see

 

 

 

 

“Surface Pulse Not Found” on page 7-5

 

 

 

 

 

Integral display does not work.

 

 

•

Check the display configuration

 

 

 

• Check loop power

 

 

 

•

Check Display connection

 

 

 

• Contact Emerson Process Management

 

 

 

 

Service Department(1)

FOUNDATION Fieldbus Card to

 

 

•

Verify Device Mode setting, should be

Transmitter Communication Fault

 

 

 

FOUNDATION Fieldbus

 

 

 

 

(Parameter: ENV_DEVICE_MODE)

 

 

 

• Restart method from Resource Block

 

 

 

• Reboot gauge (Cycle Power)

 

 

 

 

Level Measurement Failure

 

 

• Check Power Supply

 

 

 

•

Check the gauge configuration (Transducer

 

 

 

 

Block)

 

 

 

•

Check that the mechanical installation is

 

 

 

 

correct

Temperature Measurement Failure

 

 

• Check ambient temperature(2)

 

 

 

•

Restart gauge

 

 

 

• Contact Emerson Process Management

 

 

 

 

Service Department

 

 

 

 

Volume Measurement Failure

 

 

• Restart gauge

 

 

 

• Check gauge configuration using PC Based

 

 

 

 

configuration tool

No surface echo

 

 

•

Check signal strength

 

 

 

•

Restart transmitter

 

 

 

• See “Surface Pulse Not Found” on

 

 

 

 

page 7-5

 

 

 

 

 

DB Error/ Microwave Unit Error/

 

 

•

Restart transmitter

Configuration Error/ Other Error

 

 

•

Set database to default; load default

 

 

 

 

Database

 

 

 

•

Download Application Software

 

 

 

•

Call Service Center

SW Error/ Display Error/ Analog Out

 

 

•

Restart transmitter

Error

 

 

•

Call Service Center

 

 

 

 

 

(1)A malfunctioning display panel may only be replaced by service personnel at the Emerson Process Management Service Department. A display must not be replaced when the transmitter is in operation.

(2)If the 5300 transmitter has been exposed to temperatures outside the specified limits, the device may stop its normal operation.

7-34

Page 164
Image 164
Emerson Process Management 5300 manual Surface Pulse Not Found on