Rosemount 5300 Series

Reference Manual

00809-0100-4530, Rev BA July 2009

Measurement Status

Measurement Status messages that may appear on the Integral Display, on the 375 Handheld Communicator, in DeltaV, or in RRM are shown in Table 7-7:

Table 7-7. Measurement status.

Message

Description

Action

Full tank

The level measurement is in Full Tank

No action needed.

 

state. The transmitter waits for the surface

 

 

echo to be detected at the top of the tank.

 

Empty tank

The level measurement is in Empty Tank

No action needed.

 

state. The transmitter waits for the surface

 

 

echo to be detected at the bottom of the

 

 

tank.

 

Probe missing

Probe is not detected.

Check that the probe is correctly

 

 

mounted. Check the connection between

 

 

probe and transmitter head.

Seal contaminated

Suspected contamination of the seal has

Check if the seal connection with the

 

been detected.

probe is contaminated.

Reference pulse calculated

The position of the reference pulse is

No action needed.

 

calculated from the internal reference

 

 

pulse.

 

Reference pulse invalid

An error in the reference pulse in the last

Check Warning messages. If MicroWave

 

sampled tank signal.

Module (MWM) Warning is active, this

 

 

might indicate a transmitter error. Contact

 

 

Emerson Process Management Service

 

 

Department.

DeltaF not at setpoint

The DeltaF is not correctly regulated.

Check Warning Messages. If MicroWave

 

 

Module (MWM) Warning is active, this

 

 

might indicate a transmitter error. Contact

 

 

Emerson Process Management Service

 

 

Department.

Tank signal clip warning

The last Tank Signal was clipped.

Check Warning Messages. If MWM

 

 

Warning is active, this might indicate a

 

 

transmitter error. Contact Emerson

 

 

Process Management Service

 

 

Department.

No surface echo found

The Surface Echo Pulse cannot be

Check if the configuration can be

 

detected.

changed so that the surface echo can be

 

Possible cause:

tracked in this current region.

 

• Wrong surface threshold

View the Echo Curve plot and check

 

• Liquid level in Transition Zone or

surface threshold.

 

below probe end

 

Predicted level

The presented level is predicted. The

Check if the configuration can be

 

surface echo could not be detected.

changed so that the surface echo can be

 

 

tracked in this current region.

 

 

View the Echo Curve plot and check

 

 

surface threshold.

No reference echo

The Surface Echo Pulse cannot be

Check if the configuration can be

 

detected.

changed so that the surface echo can be

 

 

tracked in this current region.

Reduced reference echo

The reference echo has been found with

No action needed.

 

reduced amplitude.

 

In full tank state

The level measurement is in the full tank

No action needed.

 

state, waiting for a surface echo detection

 

 

at the top of the tank.

 

Sampling failed

The sampling of the last tank signal failed.

Check Warning Messages.

Invalid volume value

The given volume value is invalid. The

Check Volume Status for details.

 

given measurements are simulated.

 

7-38

Page 168
Image 168
Emerson Process Management 5300 manual Measurement Status