Reference Manual

00809-0100-4530, Rev BA July 2009

Rosemount 5300 Series

Device Status

Device Status messages that may appear on the Integral Display, on the 375 Field Communicator, or in RMM are shown in Table 7-4:

Table 7-4. Device status.

Message

Description

Action

Running Boot Software

The application software could not be

Contact Emerson Process

 

started.

Management Service Department.

Device Warning

A device warning is active.

See Warning Messages for details.

Device Error

A device error is active.

See Error Messages for details.

Sim Mode 0 Active

The simulation mode is active.

Turn off the simulation mode in RRM,

 

 

select Tools, Simulation Mode, and

 

 

click the Stop button.

Advanced Simulation Mode

The advanced simulation mode is

To turn off the Advanced Simulation

Active

active.

mode, set Holding Register 3600=0

 

 

(see “Viewing Input and Holding

 

 

Registers” on page 7-27).

Interface Invalid

The interface measurement is invalid.

Check the Error Messages, Warning

 

 

Messages, and the Interface Status

 

 

for details.

Invalid Measurement

The level measurement is invalid.

Check Error Messages, Warning

 

 

Messages, and Measurement Status

 

 

for details.

User Register Area Write

The configuration registers are write

Use the Lock/Unlock function to turn

Protected

protected.

off the write protection (see “Write

 

 

Protecting a Transmitter” on

 

 

page 7-26).

Write Protected Jumper Set

Write protection jumper on the display

Remove the write protection jumper.

 

is enabled.

 

Factory Settings Used

The factory default configuration is

The transmitter has lost its calibration.

 

used.

Contact Emerson Process

 

 

Management Service Department.

Probe missing

Probe is not detected.

Check that the probe is correctly

 

 

mounted. Check the connection

 

 

between probe and transmitter head.