Emerson Process Management 5300 Analog Input AI Function Block, Transducer Block Xderr messages

Models: 5300

1 324
Download 324 pages 46.88 Kb
Page 175
Image 175

Reference Manual

00809-0100-4530, Rev BA July 2009

Rosemount 5300 Series

Transducer Block

Table 7-16. Transducer Block BLOCK_ERR messages

This section describes error conditions found in the Sensor Transducer Block.

Condition Name and Description

Other

Out of Service: The actual mode is out of service

Table 7-17. Transducer Block XD_ERR messages

Condition Name and Description

Electronics Failure: An electrical component failed

I/O Failure: An I/O failure occurred

Data Integrity Error: Data stored in the device is no longer valid due to a non-volatile memory checksum failure, a data verify after write failure, etc.

Algorithm Error: The algorithm used in the transducer block produced an error due to overflow, data reasonableness failure, etc.

Analog Input (AI) Function Block

Table 7-18. AI BLOCK_ERR Conditions

This section describes error conditions that are supported by the AI Block. Read Table 7-19to determine the appropriate corrective action.

.

Condition

Condition Name and Description

Number

 

0

Other

1

Block Configuration Error: the selected channel carries a measurement that

 

is incompatible with the engineering units selected in XD_SCALE, the L_TYPE

 

parameter is not configured, or CHANNEL = zero

3

Simulate Active: Simulation is enabled and the block is using a simulated

 

value in its execution

7

Input Failure/Process Variable has Bad Status: The hardware is bad, or a

 

bad status is being simulated

14

Power Up

15

Out of Service: The actual mode is out of service

7-45

Page 175
Image 175
Emerson Process Management 5300 manual Analog Input AI Function Block, Transducer Block Xderr messages, Power Up