Reference Manual

00809-0100-4530, Rev BA July 2009

Rosemount 5300 Series

BASIC CONFIGURATION USING DELTAV

The Rosemount 5300 Series supports DD Methods for DeltaV to facilitate transmitter configuration. The following description shows how to use DeltaV with the AMS application to configure the Rosemount 5300 Series. The corresponding FOUNDATION Fieldbus commands are also shown.

To configure the Rosemount 5300 with DeltaV:

1.Select DeltaV>Engineering>DeltaV Explorer from the Start menu.

2.Navigate through the file structure to find the 5300 transmitter

3.Click the right mouse button on the 5300 transmitter icon and choose Properties.

4.The Fieldbus Device Properties window lets you enter Device Tag and Description. This information is not required for the operation of the transmitter and can be left out if desired.

General information such as device type (5300), manufacturer, device ID are presented. The Rosemount 5300 Series device ID consists of the following components:

Manufacturer ID-Model-Serial Number. Example: 0011515300 Radar T2-0x81413425.

Check that the information complies with the ordering information.

5.Select the desired transmitter in the DeltaV Explorer and choose the Configure option.