Specifying Display Panel Variables

It is possible to specify the variables to be presented on the Display Panel (LCD).

Using a Handheld Communicator

For a 375 Handheld Communicator, the LCD settings are available with: HART command [2, 2, 3].

FOUNDATION Fieldbus parameters: TRANSDUCER 1100>LCD_PARAMETERS.

Using Rosemount Radar Master (RRM)

The LCD tab in the General window lets you specify which variables to view on the Display Panel screen:

1.Choose the General option from the Setup menu, or click the General icon in the Device Configuration window.

Device Config

General

2. Select the LCD tab.

Figure 6-2. RRM lets you specify variables for the 5300 Display Panel.

3.Select the variables to be shown on the display panel. The LCD will alternate between the selected items.

The available LCD parameters are listed in Table 6-1 on page 6-6.

4.Click the Store button to save the LCD settings in the transmitter database.