open the FCU Properties/Slave Database window.

Reference Manual

Rosemount 2410

300530EN, Rev BA September 2012

Symptom

Possible cause

 

Action

 

 

 

 

TankMaster does not present

Incorrect configuration of the 2160 FCU

Check the Modbus communication addresses in the

measurement data from one or

slave database

 

2160 FCU slave database. In TankMaster WinSetup

more devices connected to the

 

 

open the FCU Properties/Slave Database window.

Tankbus. The devices

 

 

See the Raptor System Configuration Manual

communicate on the Tankbus and

 

 

(Document no. 300510EN) for more information on how

appear in the Device Live List.

 

 

to configure the 2160 FCU slave database.

 

 

 

 

 

Incorrect configuration of the 2410 tank

Check the 2410 tank database; ensure that the device

 

database

 

is available and mapped to the right tank.

 

 

Check the 2410 tank database configuration; verify that

 

 

 

the ATD Modbus address is equal to the 2410 Temp

 

 

 

Modbus address in the FCU Slave Database.

 

 

Check the 2410 tank database configuration; verify that

 

 

 

the Level Modbus address is equal to the 2410 Level

 

 

 

Modbus address in the FCU Slave Database.

 

 

• See the Raptor System Configuration Manual

 

 

 

(Document no. 300510EN) for more information on how

 

 

 

to configure the FCU 2160 slave database and the

 

 

 

2410 tank database.

 

 

 

 

 

Software or hardware failure

Check diagnostics information, see “Diagnostics” on

 

 

 

page 6-7.

 

 

Check Device Status input register, see “Device Status”

 

 

 

on page 6-23.

 

 

• Contact Emerson Process Management/Rosemount

 

 

 

TankGauging service department.

 

 

 

 

 

Too many devices connected to the

Check the model code to find out what type of

 

Tankbus

 

2410 Tank Hub that is used: Single tank or Multiple tank

 

 

 

version.

 

 

Change to a 2410 Tank Hub for multiple tanks.

 

 

 

 

Incorrect temperature reading

Configuration error

Check configuration of the temperature transmitter; in

from temperature transmitter

 

 

TankMaster Winsetup open Properties for the ATD

 

 

 

device associated with the tank.

 

 

• See the Raptor System Configuration Manual

 

 

 

(Document no. 300510EN) for more information on how

 

 

 

to configure ATD devices such as a Rosemount 2240S

 

 

 

Multi-Input Temperature Transmitter.

 

 

 

 

Measurement units are not compatible

If default database is loaded to the 2410 Tank Hub, do one

 

with host system

of the following:

 

 

in TankMaster WinSetup verify system units and

 

 

 

re-install the tank associated with the 2410 Tank Hub

 

 

update Holding Registers with correct measurement

 

 

 

units

 

 

 

 

 

Hardware failure

Check diagnostics information, see “Diagnostics” on

 

 

 

page 6-7.

 

 

Check temperature elements.

 

 

• Contact Emerson Process Management/Rosemount

 

 

 

TankGauging service department.

 

 

 

 