Holding and Input Registers for Volume Configuration

Reference Manual

300530EN, Rev BA September 2012

Rosemount 2410

Holding and Input Registers for Volume Configuration

Table C-4. Rosemount 2410 Holding registers for volume configuration

Holding registers 4300 to 4732 are used for volume configuration. The different parameters are given in Table C-4below (see “Viewing Input and Holding Registers” on page 6-2for more information on how to view and edit Holding Registers).

When the Rosemount 2410 is configured for volume calculations the resulting volume values are available in input register area IR3400 to IR3458, IR4700 to IR4710, and IR30000 to IR38000 as illustrated in Figure C-11 on

page C-16.

Name

Holding Register no.

Description

Volume control

4300

 

 

 

0: None

Tank Geometry

4302

 

 

1: Strapping table

 

 

2: Sphere

 

 

3: Horizontal cylinder

 

 

4: Vertical cylinder

Strap table length

4304

Number of strapping table points used

 

 

Distance from zero level to the tank bottom

Zero Level To Bottom

4306

L1

4308

Tank diameter

 

 

Tank length (for horizontal cylinder)

L2

4310

Interpolation method

4314

0: linear

 

 

1: Quadratic

 

 

Strapping table offset. You can use this function to shift

Level offset

4316

 

 

the zero level (empty tank) from the Datum Plate to the

 

 

bottom of the tank. The Level Offset will be added to the

 

 

measured level and then used to find the corresponding

 

 

volume value in the strapping table. A positive Level

 

 

Offset value will increase the displayed volume.

Volume offset

4318

Strapping table volume offset. Use this function to include

 

 

product volume below the zero level.

 

 

This offset will be added to the calculated volume.

 

 

Note: the Volume Offset is added when predefined tank

 

 

shapes are used as well.

Volume unit

4320

40: Us Gallons

 

 

41: Liter

 

 

42: UK Gallons

 

 

43: Cubic Meter

 

 

46: Barrels

 

 

112: Cubic Feet

Tank no.

4322

0: not active

(The 2410 Tank

 

1: tank 1

Database shows which

 

2: tank 2

devices are mapped to

 

n: tank n

the different tanks)

 

10: tank 10

 

 

Level value for strapping table point no. 0

Strap table level 0

4334

Strap table volume 0

4336

Volume value for strapping table point no. 0

 

 

Level value for strapping table point no. 1

Strap table level 1

4338

Strap table volume 1

4340

Volume value for strapping table point no. 1

 

 

Level value for strapping table point no. 99

Strap table level 99

4730

Strap table volume 99

4732

Volume value for strapping table point no. 99

Appendix C. Advanced Configuration

C-15

Page 135
Image 135
Emerson Process Management Rosemount 2410 manual Holding and Input Registers for Volume Configuration, Reference Manual