6.3 TROUBLESHOOTING

Reference Manual

Rosemount 2410

300530EN, Rev BA September 2012

6.3 TROUBLESHOOTING

Table 6-3. Troubleshooting chart

Symptom

Possible cause

 

Action

 

 

 

 

No contact with the

Wiring

Check that wires are properly connected to the

Rosemount 2410 Tank Hub

 

 

terminals.

 

 

Check for dirty or defective terminals.

 

 

Check wire insulation for possible short circuits to

 

 

 

ground.

 

 

Check that the 2410 Tank Hub is connected to the right

 

 

 

communication port on the control room PC (if no FCU

 

 

 

is used).

 

 

 

 

 

RS485 wiring

Check for proper polarity at the terminals.

 

 

 

 

Field Bus Modem (FBM)

• Check the LEDs for proper communication.

 

 

Check that the FBM is connected to the right port on the

 

 

 

control room PC.

 

 

Check that the FBM is connected to the right port on the

 

 

 

2160 Field Communication Unit (FCU).

 

 

 

 

Connection to FCU 2160

• Check that the 2410 Primary/Secondary bus is

 

 

 

connected to the right field bus port on the FCU 2160.

 

 

Check communication port LED:s inside the 2160 Field

 

 

 

Communicaton Unit (FCU).

 

 

 

 

 

Configuration of FCU 2160

Check the communication address specified for the

 

 

 

2410 in the FCU Slave Database.

 

 

Check configuration of communication parameters for

 

 

 

the FCU Fieldbus ports.

 

 

Check that the correct communication channel is

 

 

 

selected.

 

 

 

See the Raptor System Configuration Manual

 

 

 

(Document no. 300510EN) for more information on how

 

 

 

to configure the FCU 2160.

 

 

 

 

Configuration of communication protocol

In TankMaster WinSetup/Protocol Channel Properties:

 

 

check that the protocol channel is enabled

 

 

check the protocol channel configuration (port,

 

 

 

parameters, modem).

 

 

 

 

 

Hardware failure

Check the 2410 Tank Hub; check the Error LED or the

 

 

 

integral display for information.

 

 

Check the Field Communication unit (FCU).

 

 

• Check the Field Bus Modem.

 

 

Check the communication port on the control room PC.

 

 

Check that there are no devices connected to the

 

 

 

Primary/Secondary bus which are not powered.

 

 

• Contact Emerson Process Management/Rosemount

 

 

 

TankGauging service department.

 

 

 

 

 

Software failure

Restart the 2410 by disconnecting and connecting the

 

 

 

power supply (note the communication parameters that

 

 

 

appear on the display during startup).

 

 

 

 

6-18

Section 6. Service and Troubleshooting

Page 92
Image 92
Emerson Process Management Rosemount 2410 manual Troubleshooting, Reference Manual, Symptom, Possible cause, Action