3.4.11Non-IS Terminal Block

Reference Manual

300530EN, Rev BA September 2012

Rosemount 2410

3.4.11Non-IS Terminal Block

Figure 3-17. Terminal block in the explosion-proof/flameproof compartment

XP/Exd/Exe

X1

Ground screw Power SupplyPrimary Communication Bus

Secondary Communication BusManual backgroundManual background Ground screws for

communication bus shields

Table 3-8. Terminal assignment for non-intrinsically safe side (XP/Exd/Exe)

Terminal

Designation

Function

1

N / -

Power, Neutral / DC -

2

L / +

Power, Line / DC +

3

K1 A

Relay 1 output (optional). Hardware configurable NO/NC.

4

K1 com

Relay 1 common

5

K2 A

Relay 2 output (optional). Hardware configurable NO/NC.

6

K2 com

Relay 2 common

7a/7b

P Bus B

Primary communication bus

8a/8b

P Bus A

 

9

S Pwr -

Secondary power - (optional)

10

S Pwr +

Secondary power +(optional)

11

S Bus B

Secondary communication bus (optional)

12

S Bus A

Secondary communication bus (optional)

PE

PE

Protective power supply ground

GND_1

GND_1

Housing chassis/shield Primary bus

GND_2

GND_2

Housing chassis/shield Secondary bus

Power Supply

The Rosemount 2410 accepts supply voltage 24-48 Vdc and 48-240 Vac (50/60 Hz).

Primary Communication Bus

The Rosemount 2410 communicates with a host or a FCU 2160 via TRL2 Modbus or RS-485 Modbus protocol.

Secondary Communication Bus

The secondary bus can be used for communication using a number of protocols such as TRL2 Modbus, HART 4-20 mA, Enraf, Varec and L&J.