 Simulation mode active

Reference Manual

300530EN, Rev BA September 2012

Rosemount 2410

Figure 6-4. Simulation mode active is indicated in the WinSetup workspace

Advanced SimulationManual backgroundManual backgroundManual background Simulation mode active

NOTE

Simulation continues for the specified period of time. It can also be stopped manually at any time by pressing the Stop button in the Simulation window.

Advanced Simulation

1.If a Calculate Parameter check-box is selected, the simulation parameter is calculated based on input data from the holding registers Simulation HREGS 3800 to 4056. You can simulate one or more parameters simultaneously.

To simulate Product Temperature, the temperature element positions must be configured. Right-click the auxiliary tank device (ATD) icon in the WinSetup workspace, choose the Properties option, and select the Average Temperature Calculation tab. See the Raptor System Configuration Manual (Document no. 300510EN) for more information. The resulting Product Temperature is available in input register IR2100 (tank 1). It is also available in input register area starting with IR30000 (IR30044 for tank 1).

The Volume Calculation function must be activated in order to enable advanced Volume simulation. See “Volume Configuration” on page C-14for more information.

The volume calculation result is presented in input register IR4702, IR3400 (tank 1) and in input register area starting with IR30000 (IR30148 for tank 1).

To simulate Observed Density the Hybrid Density function must be activated. See “Hybrid Density Calculation” on page C-10for more information.

The resulting Observed Density is available in input register IR3500 (tank 1). It is also available in input register area starting with IR30000 (IR30116 for tank 1).

2.Click the Start button to start simulating the selected tank parameters.

Section 6. Service and Troubleshooting

6-13

Page 87
Image 87