6.2.12Relay Output Configuration

Reference Manual

300530EN, Rev BA September 2012

Rosemount 2410

6.2.12Relay Output Configuration

Figure 6-5. Rosemount 2410 Tank Hub front view

Figure 6-6. Normally Open/Normally Closed settings for relays K1 and K2 can be configured with a jumper

To change the Normallly Open/Normally Closed settings of the K1 and K2 relays, do the following:

1. Disconnect the power supply.

Front cover

2.Remove the front cover.

3.Remove the plastic display cover.

4.Switch the jumpers to the desired settings: Normallly Open or Normally Closed.

Relay K1: NC - NO

Relay K2: NC - NO

5. Replace the plastic display cover and the front cover.

NOTE!

Ensure that o-rings and seats are in good condition prior to mounting the cover in order to maintain the specified level of ingress protection.