3.4.13Intrinsically Safe Terminal Block

Reference Manual

300530EN, Rev BA September 2012

Rosemount 2410

3.4.13Intrinsically Safe Terminal Block

Figure 3-20. Intrinsically safe terminal block

The Intrinsically safe side of the Rosemount 2410 Tank Hub connects to the Tankbus which communicates with field devices on the tank.

IS/Exi

X2

Table 3-11. Terminal assignment for intrinsically safe side

Ground screws

Terminal

Designation

Function

1a

FB +

Intrinsically Safe Tankbus positive (+) terminal

1b

FB +

Intrinsically Safe Tankbus positive (+) terminal

2a

FB -

Intrinsically Safe Tankbus negative (-) terminal

2b

FB -

Intrinsically Safe Tankbus negative (-) terminal

3

IS I/O+

IS Input/Output + HART / 4-20 mA (Secondary Bus)

4

IS I/O -

IS Input/Output - HART / 4-20 mA (Secondary Bus)

5

W3

Not used (future option)

6

W4

 

GND_1

GND_1

Housing chassis/Tankbus shield

GND_2

GND_2

Housing chassis/Tankbus shield

Tankbus

The devices on the tank communicates with the Rosemount 2410 via the intrinsically safe Tankbus. All field devices in the Raptor system have built-in communication modems for FISCO FOUNDATION fieldbus (FF) communication and will automatically communicate with the 2410 when connected to the Tankbus.

Optional Secondary Bus

In addition to the Tankbus an optional intrinsically safe bus is available for communication with devices not compatible with FOUNDATION fieldbus. It allows you to connect devices for intrinsically safe HART 4-20 mA analog input/output communication.

Section 3. Installation

3-29