6.2.6Diagnostics

Reference Manual

300530EN, Rev BA September 2012

Rosemount 2410

6.2.6Diagnostics

TankMaster WinSetup offers the option to view diagnostic registers for the Rosemount 2410 Tank Hub. The diagnostic registers are selected from available Input and Holding Registers to provide a quick overview of the current device status. For a more comprehensive troubleshooting you may use the View Input Registers function (see also section “Viewing Input and Holding Registers” on page 6-2).

To view and configure the diagnostic registers:

1.In the TankMaster WinSetup workspace select the 2410 Tank Hub icon.

2.Click the right mouse button and choose View Diagnostic Registers.

The register values in the View Diagnostic Registers window are of read only type. They are loaded from the device as the window is opened.

A grey background color of a table cell in the Value column means that the register is of either Bitfield or ENUM type. By double-clicking the cell, an Expanded Bitfield/ENUM window can be opened for this type of register.

If needed, the values can be presented as hexadecimal numbers. This applies to registers of the Bitfield and ENUM types. Select the Show in Hex check box to present Bitfield and ENUM registers as hexadecimal numbers.

The Configure button lets you open the Configure Diagnostic Registers window, allowing you to change the list of registers to be displayed in the View Diagnostic Registers window.

The Configure Diagnostic Registers window also has a Log Setup button for access to the Register Log Scheduling window which allows you to setup a log schedule for automatic start and stop of register logging. See “Logging Measurement Data” on page 6-17for more information

See the Raptor System Configuration Manual (Document No. 300510EN) for more information on the View Diagnostic Registers function.

Section 6. Service and Troubleshooting

6-7

Page 81
Image 81
Emerson Process Management Rosemount 2410 manual Diagnostics, Reference Manual