C.8.1 Delta Level Calculation

Reference Manual

300530EN, Rev BA September 2012

Rosemount 2410

C.8.1 Delta Level Calculation

Figure C-13. Arithmetic operations are configured in Holding Registers 4800 to 4879

The following example illustrates how to use TankMaster WinSetup to configure a Rosemount 2410 to calculate the difference between product levels for two tanks Tank 1 and Tank 3. The result is stored in tank measurement variable Delta_Level in Tank 1.

A Virtual Relay Output can be configured to use the measurement variable Delta_Level as source parameter to trigger the relay whenever the level difference exceeds a specified value. See “Relay Output” on page C-6for more information on how to configure relay functions for a Rosemount 2410.

 

1.

Choose subtraction.

 

2.

Put the result in Tank

 

 

Measurement Variable

 

 

TMV_Delta_Level.

 

3.

Put the result in Tank 1.

 

 

Now the result will be stored in

 

 

TMV_Delta_Level for Tank 1.

 

4.

For arithmetic operation

1

 

parameter A choose Tank

 

Measurement Variable=Level.

 

 

2

5.

Choose arithmetic operation

3

 

parameter A from Tank 1.

4

 

 

 

5

6.

For arithmetic operation

6

 

parameter B choose Tank

7

 

Measurement Variable=Level.

 

7.

Choose arithmetic operation

 

 

parameter B from Tank 3.

Figure C-14. The result is displayed in Input Register 4800 and higher

The result is displayed in Input

Register 4800.

Parameter A

Parameter B

Appendix C. Advanced Configuration

C-19

Page 139
Image 139