Symptom

Possible cause

 

Action

 

 

 

 

2410 icon in TankMaster

Simulation mode active

Stop simulation mode; open WinSetup Set Simulation

WinSetup is red

 

 

Mode window and click the Stop button.

 

 

 

 

All measurement values are

Map conflict. One or more tank

Check diagnostics information (see “Diagnostics” on

indicated with “SensFail” in the

measurement variables are mapped to

 

page 6-7) for possible Device Warning messages:

WinSetup Tank View window, and

the wrong source parameter. For

 

- in case there is a “Data Manager” warning, check

with “Error” in the WinOpi Tank

example: Vapor Temperature is mapped

 

Input Register 6244

View window.

to Manual Value.

 

- if register 6244 indicates a “TMV Mapping” warning

 

 

 

check Input Registers 6260 to 6270 for tank

 

 

 

measurement variable mapping conflicts

 

 

In TankMaster Winsetup, right-click the ATD device icon

 

 

 

associated with the current tank, and click the

 

 

 

Properties option. In the 22XX ATD window select the

 

 

 

Advanced Parameter Source Configuration tab. Check

 

 

 

that tank measurement variables are mapped to the

 

 

 

right source parameters.

 

 

 

 