Non-IS Terminal Block for SIL Safety Systems

Reference Manual

300530EN, Rev BA September 2012

Rosemount 2410

Non-IS Terminal Block for SIL Safety Systems

For Safety Integrity Level (SIL) systems the Rosemount 2410 has a terminal block on the Non-IS side with connection to a SIL Alarm Relay output.

Figure 3-18. Non-IS (XP/Exd/Exe) terminal block

XP/Exd/Exe

Ground screw

Ground screws

SIL Relay

Table 3-10. Terminal assignment for SIL version of the 2410 non-IS terminal block

Terminal

Designation

Function

1

N / -

Power, Neutral / DC -

2

L / +

Power, Line / DC +

3

K1 A

Relay 1 output (optional). Hardware configurable NO/NC.

4

K1 com

Relay 1 common

5

K2 A

Relay 2 output (optional). Hardware configurable NO/NC.

6

K2 com

Relay 2 common

7a/7b

P Bus B

Primary communication bus

8a/8b

P Bus A

 

9

 

Not used

10

 

Not used

11

Alarm B

SIL Alarm Relay B

12

Alarm A

SIL Alarm Relay A

PE

PE

Protective power supply ground

GND_1

GND_1

Housing chassis/shield Primary bus

GND_2

GND_2

Housing chassis/shield Secondary bus

Section 3. Installation

3-27

Page 53
Image 53